INSTALLATION, Continued

SPECIAL REQUIREMENTS FOR INTERCONNECTED ALARMS

Failure to meet any of the above requirements could damage the units and cause them to malfunction, removing your protection.

AC and AC/DC Smoke/CO Alarms can be interconnected. Under AC power, all units will alarm when one senses smoke or CO. When power is interrupted, only the AC/DC units in the series will continue to send and receive signals.

AC powered Smoke/CO Alarms will not operate. See “Smart Interconnect” Feature.

Interconnected units can provide earlier warning of a Smoke/CO problem than stand-alone units, especially if the problem starts in a remote area of the dwelling. If any unit in the series senses Smoke/CO, all units will alarm. To determine which Smoke/CO Alarm initiated an alarm, refer to the table.

During an Alarm:

On Initiating Alarm(s) – Red LED(s) flashes (flash) rapidly

On All Other Alarms – Red LED is Off

After an Alarm (Latching):

On Initiating Alarm(s) – Green LED(s) On, Red LED(s) flash once every 5 seconds

On All Other Alarms – Green LED(s) On, Red LED(s) is Off

Compatible Interconnected Units

Interconnect units within a single family residence only. Otherwise all households will experience unwanted alarms when you test any unit in the series. Interconnected units will only work if they are wired to compatible units and all requirements are met. This unit is designed to be compatible with: BRK Electronics® Smoke Alarm Models 9120, 9120B, 7010, 7010B, 7020B, 4120, 4120B, 4120SB, 4919, 2002RAC, 100S, 5919, 5919TH; BRK Electronics® Heat Alarm Models HD6135F, HD6135FB; BRK Electronics® CO Alarm Models CO5120BN, CO5120PDBN; Smoke/CO Alarm Model SC6120B, SC9120B; and First Alert® Smoke Alarm Models SA4120, SA4120B, SA4121B, SA4919B, SA100B, SC7010B, SC7010BV; Accessory devices models RM3, RM4, SL177.

Interconnected units must meet ALL of the following requirements:

A maximum of 18 compatible BRK Electronics® Smoke, Heat or CO Alarms may be interconnected. No more than 12 of the 18 can be Smoke Alarms per NFPA 72.

The same fuse or circuit breaker must power all interconnected units.

The total length of wire interconnecting the units should be less than 1000 feet (300 meters). This type of wire is commonly available at Hardware and Electrical Supply stores.

All wiring must conform to all local electrical codes and NFPA 70 of the National Electrical Code. Refer to NFPA 72, NFPA 101, and/or your local building code for further connection requirements.

A}

5

4

3

2

1

6￿

78￿} B

5

4

3

1

 

A. Unswitched 120VAC

 

B. To Additional Alarms,

 

 

60 Hz source

 

Maximum = 18 Alarms

 

 

 

 

 

 

 

 

 

 

 

 

1.

Smoke/CO Alarm

4.

Wire Nut

7. Interconnect Wire

2.

Ceiling or Wall

5.

Junction Box

(Orange)

3.

Power Connector

6. Neutral Wire (White)

8. Hot Wire (Black)

 

 

 

 

 

 

4

Page 4
Image 4
First Alert UL217 user manual Special Requirements for Interconnected Alarms, During an Alarm, After an Alarm Latching

UL217 specifications

The First Alert UL217 is a state-of-the-art smoke and fire alarm designed to provide advanced safety and security for homes and businesses. This model adheres to rigorous standards set by Underwriters Laboratories (UL), ensuring reliability and peak performance for fire detection. One of the standout features of the First Alert UL217 is its use of photoelectric sensing technology. Unlike traditional ionization alarms, which primarily detect fast-flaming fires, photoelectric sensors excel at identifying smoldering fires, which are often more dangerous as they can produce poisonous gases long before flames are visible.

Another significant characteristic of the UL217 is its smart dual-sensor system. This innovative feature combines both photoelectric and ionization technologies, offering comprehensive protection against a wide range of fire types. This dual-action approach ensures that users are alerted to both quick-flame fires and slow-smoldering fires, thus enhancing the overall safety of a living environment.

The UL217 also includes a 10-year sealed battery. This maintenance-free power source eliminates the need for regular battery replacements, allowing homeowners and business operators to enjoy peace of mind knowing their alarms will perform effectively without the hassle of changing batteries. The sealed battery lifespan is designed to last for the entire life of the unit, typically around a decade.

The design of the First Alert UL217 is user-friendly, featuring an intuitive test/silence button that allows users to quickly check the functionality of the alarm. An innovative feature called “Smart Technology” reduces the likelihood of false alarms caused by cooking smoke or steam, ensuring fewer disturbances while maintaining vigilant fire monitoring.

Additionally, the UL217 is equipped with a loud 85-decibel alarm that effectively alerts occupants in the event of a fire. The alarm sound is specifically designed to be heard over typical household noises, ensuring that individuals are promptly informed of potential danger.

In summary, the First Alert UL217 smoke alarm combines cutting-edge technology, durability, and user-centric design to provide effective fire detection and life-saving alerts. Its dual-sensor technology, long-lasting battery, and reliable performance make it an essential component of any comprehensive fire safety plan. Whether in a residential setting or a commercial environment, the UL217 stands as a guardian against the threat of fire.