Venting Installation
Optional Outside air Kit (Model ak4/ak4f)
The installation of an outside air kit should be performed during the rough framing of the fireplace due to the nature of it's location. Outside combustion air is accessed through a vented crawl space (AK4F) or through a sidewall (AK4).
CAUTION: Combustion air inlet ducts shall not terminate in attic space.
Secure to Collars with Metal Tape, Screws or Straps (Min. 1/4" x 20" size)
Air Inlet
Location
Must Allow For Bushes or Snow
| Air Inlet | |
| Eyebrow | |
Vented Crawl Space | Vent Hood | |
Required for | ||
(Check Local Codes | ||
Wall Installation | ||
Before Installing in a | ||
| ||
Vented Crawl Space) |
| |
Figure 5 - Outside Air Kit |
Chimney Pipe
The FMI PRODUCTS, LLC chimney system consists of 12", 18", 24", 36" and 48" snap- lock,
WARNING: The opening in the collar around the chimney at the top of the fireplace must not be obstructed. Never use blown insulation to fill the chimney enclosure.
LINEAL GAIN
PART NO. | DESCRIPTION | GAIN | |
Georgian | Fireplace | 66 1/2" | |
Pipe Section | 10 5/8" | ||
|
| ||
Pipe Section | 16 5/8" | ||
|
| ||
Pipe Section | 23 5/8" | ||
|
| ||
Pipe Section | 34 5/8" | ||
|
| ||
Pipe Section | 46 5/8" | ||
|
| ||
Round Termination | 7 3/4"* | ||
|
| ||
Square | 7" to 15"* | ||
| with Slip Section |
|
*The lineal gain for the terminations is mea- sured to the flue gas outlet height.
15" Galvanized
Outer Pipe
12 3/8" | Hemmed |
Stainless | End |
| |
Inner Pipe |
|
Figure 6 - Lineal Gain
Assembly and installation of double wall chimney system
Each double wall chimney section consists of a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. Pipe sections must be assembled independently as chimney is installed. When connecting chimney directly to fireplace, the inner flue pipe section must be installed first with lanced side up. The outer pipe section can then be installed over the flue pipe section with hemmed end up. Press down on each pipe section until lances securely engage hem on fireplace starter. The wire will assure the proper spacing between inner and outer pipe sections.
Continue to assemble chimney sections as outlined above, making sure that both inner and outer pipe sections are locked together. When installing double wall
www.fmiproducts.com | 7 |