
Venting INSTALLATION
Continued
This appliance may be vented through a manufactured chimney system or a masonry chimney using a
The examples shown in Figure 9 are typical of most
Example 1: Shows the minimum allowable system height and lateral offset for a 60° or greater inclination. Code specifies that offsets at 60° or greater are considered horizontal and must follow the 75% rule for lateral to total vertical system height. Codes also allows only one offset in the total system when at 60° or greater. The total vertical height in this example represents the minimum height of 8 feet and therefore the allowable lateral is 6 feet when the 75% rule applies. If the lateral length must exceed 75% then the system must be sized in accordance with the Category I venting tables.
Example 2: Shows a multiple offset each at 45° of inclination. Multiple offsets are permitted if they do not exceed 45° of inclination. The total lengths of the two offsets are not required to meet the 75% allowable rule.
Example 3: Shows a single offset at 45° of inclination and therefore the lateral length at 10 feet of offset does not have to meet the 75% rule.
In each case the offsets must be supported and firestops must be positioned wherever the vent must pass through a
Vent terminations must be located in accordance with height and proximity rules of NFPA No. 54. These rules apply to vents at 12" diameter or less and require a minimum height in accordance with the roof pitch and a minimum of 8 feet distance from a vertical wall or obstruction (see Figure 10, page 10).
If venting horizontally through a side wall becomes necessary, a listed thimble approved for use with
Some codes areas allow the use of existing B- type vent systems if the system is at or above the recommended diameter of the flue.
The flue connection must be made using listed
| Listed |
|
|
|
|
| Vent Cap |
| Listed | Listed | |
|
|
| |||
|
|
| Vent Cap | ||
|
|
| Vent Cap | ||
|
|
|
| ||
Maintain |
| Maintain |
|
|
|
Listed |
| Listed |
|
|
|
Clearance |
| Clearance |
|
| Maintain |
|
| Support Each | Maintain |
| Listed |
|
| Lateral At | Listed |
| Clearance |
| 60° | Least Every | 45°Clearance |
|
|
8' Position |
| 6 Feet | 12' Min. | 45° | 10' |
6' |
| Position | |||
12' Min. Firestop | Position | Firestop |
| 12' Min. | |
|
| ||||
|
| Firestop | 45° |
|
|
|
|
|
|
| |
| Maintain |
| Maintain |
| Maintain |
| Listed |
| Listed |
| Listed |
| Clearance | Clearance |
| Clearance |
EXAMPLE 1 | EXAMPLE 2 | EXAMPLE 3 |
| Figure 9 - Typical |
|
www.fmiproducts.com | 9 |