Check that the currents in the individual phases of a
Starter | L1 | L2 | L3 |
cable (1) | black | yellow | red |
cable (2) | red | black | yellow |
|
|
|
|
cable (3) | yellow | red | black |
|
|
|
|
Then subtract the average of the readings from the highest. The difference, expressed as a percent of the average must not exceed 10%. Note that the highest reading must not exceed the maximum permissible for the motor.
EXAMPLE:
Phase 1 | 54.0 amp |
Phase 2 | 55.0 amp |
Phase 3 | 60.0 amp |
Average: | 56.3 amp |
%Unbalance = 60 - 56.3 x 100 56.3
=3.7 x 100 = 6.6%
56.3
WARNING
FAILURE TO GROUND THE UNIT PROPERLY CAN RESULT IN SERIOUS OR FATAL SHOCK. REFER TO ELECTRICAL CODE REQUIREMENTS.
Should the unbalance exceed 10%, ask the power company to improve the voltage balance between the incoming lines.
5- Use a voltmeter to check the voltage at the starter while the pump is running. The average must be within 10% of the motor rating, and the maximum variation of any phase of a
exceed 1%.
6- Continue to run the pump until the drawdown of the water in the well becomes stable. Should the water level drop to the pump intake to admit air, use one or more of the following methods to protect installation.
(a)Install additional riser pipe to place pump lower in the well if possible.
(b)Use a cock or similar valve in the discharge line to throttle the pump output to suit the yield of the well.
(c)Install FLOATLESS LIQUID LEVEL CONTROL.
(d) Use a pressure switch with a low water protection or a separate
(e)Replace the pump with smaller unit to avoid over pumping the well.
*CAUTION*
NEVER RUN THE PUMP UNLESS IT IS COMPLETELY SUBMERGED IN WATER.
Damage can occur to both pump and motor, in addition, air drawn into the pump can cause
H. ACCESSORIES WITH INSTALLATION
LIGHTNING ARRESTERS
Install lightning arresters to protect the motor from the effects of electrical storms. Although they will not give protection against direct stirkes they will ground the surges caused in transmission lines by surrounding storms.
One arrester is sufficient for a
RELIEF VALVE
Always install a relief valve if the pump is capable of developing pressures in the discharge system greater than the pressure ratings of individual components. The relief valve must be large enough to handle the pump output at the relief pressure.
6