ERROR CONTENTS (indoor unit)

ERROR CONTENTS (indoor unit)

(1)Stop the air conditioner operation.

(2)Press the master control button and the fan control button simultane- ously for 2 seconds or more to start the test run.

Test run display

(3) Press the start/stop button to stop the test run.

[SELF-DIAGNOSIS]

When the error indication "E:EE" is displayed, follow the following items to perform the self-diagnosis. "E:EE" indicates an error has occurred.

1. REMOTE CONTROLLER DISPLAY

(1)Stop the air conditioner operation.

(2)Press the set temperature buttons Manual backgroundManual backgroundManual background simultaneously for 5 sec- onds or more to start the self-diagnosis.

Refer to the following tables for the description of each error code.

Unit number (usually 0)

Error code

SU MO TU WE TH FR SA

Ex. Self-diagnosis

(3)Press the set temperature buttons Manual backgroundManual backgroundManual background simultaneously for 5 sec- onds or more to stop the self-diagnosis.

Error code

 

 

Error contents

00

Communication error

(indoor unit

 

remote controller)

 

 

 

 

01

Communication error

(indoor unit

 

outdoor unit)

 

 

 

 

02

Room temperature sensor open

 

 

 

 

 

 

03

Room temperature sensor short-circuited

 

 

 

 

 

 

04

Indoor heat exchanger temperature sensor open

 

 

 

 

 

 

05

Indoor heat exchanger temperature sensor short-

circuited

 

06

Outdoor heat exchanger temperature sensor

 

 

 

 

 

 

08

Power source connection error

 

 

 

 

 

 

09

Float switch operated

 

 

 

 

 

 

0A

Outdoor temperature sensor

 

 

 

0c

Discharge pipe temperature sensor

 

 

 

 

 

 

 

11

Model abnormal

 

 

 

 

 

 

 

12

Indoor fan abnormal

 

 

 

 

 

 

 

Error code

 

 

Error contents

13

Outdoor signal abnormal

 

 

 

 

 

 

14

Excessive outdoor pressure (permanent stop)

 

 

 

 

 

 

15

Compressor temperature sensor

 

 

 

 

 

 

16

Pressure switch error

 

 

 

 

 

 

 

17

IPM error

 

 

 

 

 

 

 

 

18

CT error

 

 

 

 

 

 

 

19

Active filter module (AFM) error

 

 

 

 

 

 

1A

Compressor does not operate

 

 

 

 

 

 

1b

Outdoor unit fan error

 

 

 

 

 

 

1c

Communication error

(inverter

 

multicontroller)

 

1d

2 way valve sensor error

 

 

 

 

 

 

1E

Expansion valve error

 

 

 

 

 

 

1F

Connection indoor unit error

 

 

 

 

 

 

 

2. CHECKING DRAINAGE

To check the drain, remove the water cover and fill with 2 to 3 of water as shown in figure.

The drain pump operates when operating in the cooling mode.

Drain pipe

Water cover