ERROR DETECTION
Error | Display | Error | ||
Operation | Timer LED | |||
|
| |||
| LED |
|
| |
|
| 2 flash | Serial signal (reverse) error, at operation start up | |
|
|
|
| |
|
| 3 flash | Serial signal (reverse) error, during oeration | |
|
|
|
| |
Serial signal error | Normal | 4 flash | Serial signal (forward) error, at operation start up | |
|
|
|
| |
|
| 5 flash | Serial signal (forward) error, during operation | |
|
|
|
| |
|
| 8 flash | Wired remote controller error | |
|
|
|
| |
Indoor unit thermistor error | 2 flash | 2 flash | Indoor temperature thermistor open / short | |
|
| |||
3 flash | Heat exchanger middle thermistor open / short | |||
|
| |||
|
|
|
| |
|
| 2 flash | Discharge thermistor open / short | |
|
|
|
| |
Outdoor unit thermistor error | 3 flash | 3 flash | Heat exchanger thermistor open | |
|
| |||
4 flash | Outdoor temperature thermistor open / short | |||
|
| |||
|
|
|
| |
|
| 8 flash | Compressor temperature thermistor open / short | |
|
|
|
| |
|
| 2 flash | Forced automatic SW welded | |
|
|
|
| |
|
| 3 flash | Main relay welded | |
|
|
|
| |
Indoor unit control error | 4 flash | 4 flash | Power interruption error | |
|
|
|
| |
|
| 7 flash | VDD permanent stop protection | |
|
|
|
| |
|
| 8 flash | reverse VDD permanent stop protection | |
|
|
|
| |
|
| 2 flash | Current trip error | |
|
|
|
| |
Outdoor unit control error | 5 flash | 3 flash | CT abnormal | |
|
| |||
5 flash | Compressor location detection error | |||
|
| |||
|
|
|
| |
|
| 6 flash | Outdoor unit fan drive system abnormal | |
|
|
|
| |
Indoor fan motor error | 6 flash | 2 flash | Abnormal lock | |
|
| |||
3 flash | Abnormal rotation | |||
|
| |||
|
|
|
| |
|
| 2 flash | Discharge Temperature abnormal | |
|
|
|
| |
Refrigerant cycle error | 7 flash | 3 flash | Cooling high pressure abnormal rise | |
|
|
|
| |
|
| 5 flash | Pressure switch trouble | |
|
|
|
| |
|
| 2 flash | Active filter voltage trouble (second time) | |
Optional function error | 8 flash |
|
| |
3 flash | Active filter voltage trouble (first time) | |||
|
|
|
| |
|
| 4 flash | PFC circuit error | |
|
|
|
| |
Model information error | 0.1 sec on/off | 0.1 sec on/off | Model information error | |
|
|
|
|
2010.02.26 | 16 |