Ductless Split Systems
Ceiling and floor installed heat pumps
Specifications
PERFORMANCE RATINGS
SYSTEM MODEL NO. |
| S24YF | S36YF | C24YF |
INDOOR MODEL |
| MS24Y3F | MS36Y3F | MC24Y3F |
OUTDOOR MODEL |
| MR24UY3F | MR36Y3F | MR24UY3F |
|
|
|
|
|
Capacity Cooling | Btu | 22200 | 34100 | 22200 |
Capacity Cooling Min - Max | Btu | |||
|
|
|
|
|
Sensible Heat Ratio |
| 0.62 | 0.67 | 0.64 |
Capacity Heating @ 47°F | Btu | 24,200 | 38,200 | 24,200 |
Capacity Heating Min - Max | Btu | |||
|
|
|
|
|
Capacity Heating @ 17°F | Btu | 20,100 | 27,100 | 20,100 |
HSPF |
| 8.5 | 8.5 | 8.5 |
|
|
|
|
|
SEER |
| 15 | 14 | 15 |
EER |
| 9.8 | 8.1 | 10.6 |
Moisture Removal | Pts/h | 7.4 | 7.4 | 6.4 |
|
|
|
|
|
Airflow (Low, Med, High) | CFM | 371, 436, 518 | 842, 977, 1089 | 436, 536, 618 |
Sound Rating - Indoor | 38, 43, 47 | 41, 45, 48 | 38, 43, 45 | |
|
|
|
|
|
Sound Rating - Outdoor | 53 | 54 | 53 | |
Operationg Range (heating) | °F | 0 - 115 (14 - 75) | 0 - 115 (14 - 75) | 0 - 115 (14 - 75) |
Est. Yearly Operating Cost |
| $180 | $337 | $168 |
|
|
|
|
|
ELECTRICAL DATA |
|
|
|
|
Power Source |
| |||
|
|
|
|
|
Min. Ampacity | A | 15.5 | 23 | 15.5 |
Cooling Watts | W | 2250 | 4220 | 2100 |
Max. TD Fuse/Breaker | A | 20 | 30 | 20 |
|
|
|
|
|
REFRIGERATION SYSTEM |
|
|
|
|
Refrigerant |
| R410A | R410A | R410A |
|
|
|
|
|
Compressor Type |
| Inverter (Twin Rotary) | Inverter (Twin Rotary) | Inverter (Twin Rotary) |
Connections |
| Flare | Flare | Flare |
Liquid Line O.D. | in | 3/8" | 3/8" | 3/8" |
|
|
|
|
|
Suction Line O.D. | in | 5/8" | 5/8" | 5/8" |
Factory Precharge | ft | 50' | 50' | 50' |
|
|
|
|
|
Max. Line Length | ft | 165' | 165' | 165' |
Max. Height Difference | ft | 66' | 98' | 66' |
DIMENSIONS & WEIGHT |
|
|
|
|
|
|
|
|
|
Indoor Unit |
|
|
|
|
W x H x D | in | 39" x 7 7/8" x 25 3/4" | 65 3/8" x 9 1/2" x 27 1/2" | 32 5/8" x 9 5/8" x 32 5/8" |
|
|
|
|
|
Net Weight | lbs | 62 | 106 | 75 |
Shipping Weight | lbs | 82 | 134 | 97 |
Outdoor Unit |
|
|
|
|
|
|
|
|
|
W x H x D | in | 35 3/8" x 32 5/8" x 13" | 35 3/8" x 32 5/8" x 13" | 35 3/8" x 32 5/8" x 13" |
Net Weight | lbs | 141 | 141 | 141 |
|
|
|
|
|
Shipping Weight | lbs | 154 | 154 | 154 |
NOTE: All models have low ambient capabilities
NOTE: All R410A models have 1/2˝ UNF 20 thread per inch charging and vacuuming ports. An adapter must be used for 1/4˝ gauges. Adapter part number 67270018 is available through Friedrich parts distributors.
Due to continuing research in new
Refrigeration line sets
USED WITH: | LIQUID | SUCTION | KIT# | |
|
|
|
|
|
S24YF, S36YF | 15' | 3/8” | 5/8” | T53150 |
|
|
|
| |
and C24YF | 35' | 3/8” | 5/8” | T53350 |
systems | ||||
|
|
|
|
|
Insulated line sets are available for all Friedrich split systems in 15 ft. and 35 ft. lengths. Each line set is equipped with flare nuts on both ends. Both liquid and suction lines are insulated. Line sets can be joined together with field supplied double female connectors. Each system requires one line set for each indoor unit installed. On