SECTION V — SHELL INSTALLATION
(B) THROUGH–THE–WALL INSTALLATIONS
WALL PREPARATION:
The maximum wall thickness permissible without special construction is determined by the model size to be installed. THE
OUTSIDE CABINET CONDENSER AIR INTAKE LOUVERS MUST NOT BE BLOCKED BY EXTENDING INSIDE THE WALL AREA. Observe the maximum wall thickness shown as dimension "A" in Figure J.
SPECIAL INSTRUCTIONS FOR EXTRA THICK WALLS: For installation in walls exceeding the maximum thickness shown as dimension A, the following suggested construction may apply. (See Figure J).
FIGURE J | EXTRA THICK WALL CONSTRUCTION |
15 1/8 " (384 mm) Maximum wall thickness
Condenser
Air intake
Louvers
Top view showing beveled sides for air intake. Wall below unit must also be beveled to assure proper tilt angle.
2" (51 mm) minimum Both sides
Condenser air
Intake louvers
STEP 1. CHECKING WIRING AND PLUMBING: Check all wiring and plumbing inside and outside the wall to be sure none will be broken where the hole is to be cut.
STEP 2. HOLE CONSTRUCTION: Depending on the size of the unit to be installed, layout the hole dimensions in accordance with the chart below (See Figure K). Cut and frame in the hole to the finished dimensions. Use 2" x 4" material for framing and follow the suggested typical installations in Figure L, M or N on Page 15.
NOTE: IF THE WALL CONSTRUCTION IS TYPICAL FRAME OR 2 X 4 STUDDING WITH BRICK OR STONE VENEERS, LOCATE THE HOLE NEXT TO ONE OF THE STUDS. FOR MASONRY, CONCRETE OR CINDER BLOCK WALLS, LOCATE THE HOLE FOR CONVENIENCE.
FIGURE K | HOLE SIZE REQUIREMENTS |
| ||
|
|
|
|
|
| FINISHED | SMALL |
| MEDIUM |
| DIMENSION | CHASSIS |
| CHASSIS |
|
|
|
|
|
| A |
|
|
|
|
|
|
|
|
| B |
|
| |
|
|
|
|
|
NOTE: THESE DIMENSIONS ARE FOR FINISHED HOLE SIZE
Page 14