Installation instructions for WSC sleeve
Mounting hardware provided
ITEM NO. | DESCRIPTION | QTY. |
1 | SCREW, #12A x 2" | 5 |
|
|
|
Wall preparation
STEP 1 The wall opening required for a WSC SLEEVE is 17 ¼" high by 27 ¼" wide.
STEP 2 LINTELS must be used in opening of brick veneer and masonry walls to support the material above the WSC SLEEVE. The following considerations should also be given:
Minimum Of 24" Required
From Top Of Unit To Ceiling.
Inside Wall
Minimum Of 1" Spacing |
| |
Required On All Sides | Inside | |
Of The Unit. | ||
| ||
| ⅞" Minimum Beyond Wall |
1" Minimum
3 ½" For Subbase
Figure 8
Lintels
WSC Sleeve
Drain
Extension
9⁄16" Minimum
Beyond Outside
Wall
Outside Wall
11