Fujitsu ASYA24LCC Specifications, Electrical Data, Compressor, Fan Motor, Dimensions, Weight

Models: ASYA24LCC AOYR24LCC

1 24
Download 24 pages 38.22 Kb
Page 2
Image 2

SPECIFICATIONS

INDOOR UNIT

ASYA24LCC

 

 

OUTDOOR UNIT

AOYR24LCC

 

 

COOLING CAPACITY

7.10 kW

 

 

HEATING CAPACITY

8.10 kW

 

 

ELECTRICAL DATA

POWER SOURCE

 

230 V

 

 

 

 

 

FREQUENCY

 

50Hz

 

 

 

 

 

RUNNING CURRENT

 

 

COOLING

9.7 A

 

 

 

 

 

HEATING

9.8 A

 

 

 

 

 

 

 

 

INPUT WATTS

 

 

COOLING

2,21 kW

 

 

 

 

 

HEATING

2,24 kW

 

 

 

 

 

 

 

E.E.R.

COOLING

3.21 kW

 

 

 

 

COP

HEATING

3.62 kW

 

 

 

 

MOISTURE REMOVAL

 

3.0 L/hr

 

 

 

AIR CIRCULATION -High

1,100 m3/hr

COMPRESSOR

TYPE

 

Hermetic type, 4 pole,

 

DC inverter motor, Scroll

 

 

 

 

 

DISCRIMINATION

 

5CS160XAA23

 

 

 

REFRIGERANT

R410A

1,600 g

 

 

 

FAN MOTOR

POWER SOURCE

230 V

 

 

 

 

HIGH

1,310 r.p.m.

 

 

 

INDOOR UNIT

MED

1,120 r.p.m.

 

 

LOW

940 r.p.m.

 

 

 

 

 

QUIET

830 r.p.m.

 

 

 

OUTDOOR UNIT

COOL

1,000 r.p.m.

 

 

HEAT

1,050 r.p.m.

 

 

 

 

DIMENSIONS

INDOOR UNIT

H x W x D

320 x 998 x 228

mm

 

 

 

 

OUTDOOR UNIT

H x W x D

578 x 790 x 315

mm

 

 

 

 

WEIGHT

INDOOR UNIT

Gross / Net

18 / 14 kg

 

 

 

OUTDOOR UNIT

Gross / Net

48 / 44 kg

 

 

 

NOISE LEVEL

 

HIGH

C 47 dB / H 45 dB

 

 

 

INDOOR UNIT

MED

C 41 dB / H 41 dB

 

 

LOW

C 36 dB / H 36 dB

 

 

 

 

 

QUIET

C 32 dB / H 32 dB

 

 

 

OUTDOOR UNIT

C 52 dB / H 53 dB

 

 

 

REFRIGERANT CHARGE (R410A)

Pipe Length

15 m

1,600 g

 

 

 

FULL CHARGE

20 m

1,700 g

AMOUNT

25 m

1,800 g

 

 

 

 

30 m

1,900 g

 

 

 

ADDITIONAL CHARGE

20 g / m

 

 

 

2006.03.22

1

Page 2
Image 2
Fujitsu ASYA24LCC, AOYR24LCC Specifications, Electrical Data, Compressor, Fan Motor, Dimensions, Weight, Noise Level