Chapter 3 Connections
3.4 Power Synchronized Connections
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
50
Copyright 2012 FUJITSU LIMITED P3AM-5492-04ENZ0
When connecting one or two servers
Figure 3.11 Power control using a power synchronized unit (when connecting one or two
servers)
Powering on sequence
1Power on of all the server UPS units
2Server startup
The server OS startup is suspended until the ETERNUS DX Disk storage system
startup is complete (*1).
3Issuance of command to turn on the ETERNUS DX Disk storage system from the
power synchronized unit
4ETERNUS DX Disk storage system startup
*1: The server must be set to suspend server OS startup until the ETERNUS DX Disk storage
system startup is complete.
Powering off sequence
1Shutdown of all the servers
2Shutdown of all the server UPS units
3Issuance of command to turn off the ETERNUS DX Disk storage system from the
power synchronized unit
4ETERNUS DX Disk storage system shutdown
RS232C cable
Server
ETERNUS DX
Disk storage system
PWC
UPS setting
Power synchronized unit
PWC
UPS
UPS
management
software
An instruction is
issued to turn on/off
the ETERNUS DX
Disk storage
system when AC
output/no AC output
is detected.
Turns on: 1
Turns off: 2
3
4
Turns on: 2
Turns off: 1