Chapter 2 ETERNUS DX Disk Storage System Installation
2.6 Outlet/Socket Specifications
ETERNUS DX80 S2/DX90 S2 Disk storage system User’s Guide -Site Planning-
Copyright 2013 FUJITSU LIMITED P3AM-4822-12ENZ0
39
■Power distribution units (only for regions other than EMEA&I)●Power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 1U, Max 2 enclosures connection)
Table 2.7 Specifications for power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 1U, Max 2
enclosures connection)
●Power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 6 enclosures connection)
Table 2.8 Specifications for power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 6
enclosures connection)
●Power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 8 enclosures connection)
Table 2.9 Specifications for power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 8
enclosures connection)
Output Input Remarks
Outlet type Plug type Socket type Cable length
IEC60320-C13 NEMA L6-15P NEMA L6-15R 4.0m 250V 15A
(Normal usage
<12A)
Output Input Remarks
Outlet type Plug type Socket type Cable length
IEC60320-C13 NEMA L6-20P NEMA L6-20R 4.0m 250V 20A
(Normal usage
<16A)
Output Input Remarks
Outlet type Plug type Socket type Cable length
IEC60320-C13 NEMA L6-30P NEMA L6-30R 4.0m 250V 30A
(Normal usage
<24A)