ELECTRONIC CONTROL FAILURE CODES

The GARLAND digital control has a self-diagnostic program. If a problem occurs within the digital controller, you may see one of the "F" codes.

Below is a listing of the "F" codes with explanations:

-F1-Relay output is enabled when not cooking. If this failure code appears in the display, the cook relay may be on even if the control is not cooking. The control should be replaced.

-F2-Over temperature alarm. If this failure code appears in the display the control is sensing an oven temperature 50° or more above the maximum set temperature (500°). This failure may be caused by a faulty sensor.

Check the sensor connection for loose wires.

Replace the sensor and check for proper operation.

If failure continues replace the control.

-F3-Open sensor circuit. If this failure appears in the display, the control is sensing an open circuit at the sensor input. This failure is most often caused by a poor connection or broken sensor.

Check sensor connection and leads for broken wires of loose connections. Replace sensor and check for proper operation. If failure continues replace control.

-F4-Shorted sensor circuit. If this failure appears in the display, the control is sensing a short circuit at the sensor input. This failure is most often caused by loose wires at the connection of shorted sensor leads.

Check sensor connection and leads for loose wires. Replace sensor and check for proper operation. If failure continues replace control.

-F5-Relay outputs not enabled when cooking. If this failure appears in the display the control cannot turn the relays on even when cooking. The control should be replaced.

-F6-No 60 Hz input. The control does not sense the input power. This failure mode is most often the result of a failed component in the control. However, this failure may also be the result of a very noisy power line. Look for any large electrical noise producing machinery (such as mixers, compressors, dishwashers etc.). If possible, turn these machines off. Reapply power to the oven. If the failure repeats, replace the control. If the failure does not repeat, an electronic control may not work in this application because of noise. You must isolate the supply circuit.

-F7-The control has detected that calculated EEPROM check sum is not the same as the expected check sum retrieved from the EEPROM. When the control detects this error code, it will disable outputs before the alarm sounds.

RESISTANCE vs. TEMPERATURE CHART FOR INTERNAL OVEN TEMPERATURE SENSOR

The chart below will provide the Ohms at various temperatures. This will enable you to determine if the temperature probe is operable.

The chart is in Degrees Fahrenheit. How to use chart, for 350°, read down to 300 then across to 50, answer is 1654Ohms of resistance.

TEMP

10°

20°

30°

40°

50°

60°

70°

80°

90°

 

932

953

974

995

1016

 

1038

1059

1080

1101

1122

100°

1143

1163

1184

1205

1226

 

1247

1267

1288

1309

1329

200°

1350

1370

1391

1411

1432

 

1452

1472

1493

1513

1533

300°

1553

1574

1594

1614

1634

 

1654

1674

1694

1714

1733

400°

1753

1773

1793

1813

1832

 

1852

1871

1981

1911

1930

500°

1949

1969

1988

2008

2027

 

2046

2065

2085

2104

2123

ROBERTSHAW COM6000 CONTROLLER

9

Page 9
Image 9
Garland MCO-GS-10M, MCO-GD-10M, MCO-GD-10E, MCO-GS-10E Electronic Control Failure Codes, Temp, Robertshaw COM6000 Controller

MCO-GD-10M, MCO-GS-10E, MCO-GD-10E, MCO-GS-10M specifications

Garland has made a significant mark in the market with its range of high-efficiency heaters, particularly the MCO-GS-10M, MCO-GD-10E, MCO-GS-10E, and MCO-GD-10M models. These advanced heating solutions are designed for various applications where reliability, efficiency, and versatility are essential.

The MCO-GS-10M and MCO-GD-10M models are particularly notable for their robust construction and dual-fuel capability, allowing them to utilize natural gas or propane. This flexibility ensures that users can choose the most cost-effective fuel source, making them ideal for both residential and commercial use. These models are equipped with state-of-the-art ignition systems that guarantee a swift and trouble-free start every time, minimizing downtime.

On the other hand, the MCO-GS-10E and MCO-GD-10E models are electric heaters that offer an environmentally friendly alternative without compromising performance. These units are designed with high-efficiency heating elements that ensure rapid heating while consuming less energy. Furthermore, their sleek and modern design allows them to blend seamlessly into any indoor environment, making them suitable for use in homes, offices, and other professional settings.

All four models incorporate advanced safety features, including automatic shut-off mechanisms to prevent overheating. They are designed with user-friendly controls, allowing operators to easily set the desired temperature and adjust fan speeds based on their specific heating needs.

In terms of durability, Garland has ensured that the exterior of these heaters is constructed from high-grade materials capable of withstanding harsh conditions. This ensures longevity and reduces the need for frequent replacements, providing excellent value for money.

Moreover, the technology embedded within these models, such as multi-stage heating and precise temperature controls, offers an optimal heating experience. They are designed to be energy efficient, helping consumers save on utility bills while still maintaining comfortable ambient temperatures.

Overall, the Garland MCO-GS-10M, MCO-GD-10E, MCO-GS-10E, and MCO-GD-10M units exemplify the perfect blend of innovation, efficiency, and safety. These models cater to a diverse range of heating needs while being environmentally aware, making them an excellent choice for users seeking reliable and effective heating solutions. Whether it's for home use or in a commercial setting, Garland's heaters deliver excellent performance that stands the test of time.