ETS/ETU SERIES FEATURES
GENERAL FEATURES
•19 different Btu/hr sizes and more than 100 different configurations to custom design your infrared heating system.
•CSA design certified
•Vented or indirect vented operation
•Sidewall or
•Natural and propane gas models
PULL THROUGH SYSTEM
•Products of combustion are pulled through the combustion chamber for increased radiant efficiency and greater safety
•No draft hoods, totally enclosed combustion chamber
•
•Draft inducer can be rotated 45° or 90° for sidewall venting
BURNER SYSTEM
•
•
•Inside or outside air for combustion
•Up to 50 ft. outside combustion air duct capability
•Standard 6” combustion air duct opening
•Reliable direct spark ignition system and 100% gas
•
•
•Diaphragm air switch for proof of venting before gas flow and ignition
•Diagnostic monitoring light system
•Burner inspection sight glass
RADIANT EMITTER TUBE SYSTEM
•4” O.D.
•
•Suitable for horizontal or angle mounting up to 45°
•Optional 90° elbows
•Up to 75 feet sidewall vent capacity
REFLECTOR SYSTEM
•Highly efficient aluminum reflectors with reflectivity rating of 97.5%
•Optional end, corner, side and
•Optional decorative grille
•Individual reflectors can be rotated up to 45° to direct heat where needed
•
MODEL SELECTIONS
|
| BTU/HR |
| TOTAL EMITTER LUBE LENGTH* | |||||
MODEL | INPUT | 15 FT** | 20 FT | 30 FT | 40 FT 50 FT | ||||
ETS/U 40 |
| 40,000 |
| X | X |
|
|
|
|
ETS/U 50 |
| 50,000 | X |
| X | X |
|
|
|
ETS/U 60 |
| 60,000 |
|
| X | X |
|
|
|
ETS/U 75 |
| 75,000 |
|
| X | X |
|
|
|
ETS/U 80 |
| 80,000 |
|
|
| X | X |
|
|
ETS/U 90 |
| 90,000 |
|
|
| X | X |
|
|
ETS/U 100 | 100,000 |
|
|
| X | X |
|
| |
ETS/U 110 | 110,000 |
|
|
| X | X |
|
| |
ETS/U 120 | 120,000 |
|
|
| X | X |
|
| |
ETS/U 125 | 125,000 |
|
|
| X | X | X |
| |
|
|
|
|
|
|
|
|
|
|
|
| BTU/HR |
| TOTAL EMITTER LUBE LENGTH* | ||||||
MODEL | INPUT | 30 FT | 40 FT | 50 FT | 60 FT | 70 FT 80 FT | ||||
ETS/U 130 | 130,000 | X | X | X |
|
|
|
|
| |
ETS/U 140 | 140,000 |
| X | X |
|
|
|
|
| |
ETS/U 150 | 150,000 |
| X | X |
|
|
|
|
| |
ETS/U 160 | 160,000 |
| X | X |
|
|
|
|
| |
ETS/U 175 | 175,000 |
| X | X |
|
|
|
|
| |
ETS/U 180 | 180,000 |
|
| X | X |
| X | X |
| |
ETS/U 200 | 200,000 |
|
| X | X |
| X | X |
| |
ETS/U 225 | 225,000 |
|
| X | X |
| X | X |
| |
ETS/U 250 | 250,000 |
|
| X | X |
| X | X |
| |
|
|
|
|
|
|
|
|
|
|
|
|
| *Indicate model number based on Btu/hr input (e.g., 100,000 Btu/hr), total emitter length, (e.g., 40 feet) and gas type (e.g., | natural gas). The | ||||||||
|
| unit selection for a straight tube would be |
| ||||||||
|
|
|
|
|
|
|
|
|
| ||
GAS |
| BURNER | SUPPLY PRESSURE |
|
| IGNITION |
|
| |||
TYPE |
| PRESSURE | MIN |
| MAX | VOLTAGE | AMPS | TYPE | NOTE: | For all installations higher than | |
NATURAL | 3.5” W.C. | 5” | W.C* | 14” | W.C. | 120 VAC | 2.6 | DIRECT | 2000 ft. above sea level, please consult | ||
PROPANE |
| 10” W.C. | 11” | W.C.** | 14” W.C. | 60 HZ | SPARK | the factory regarding recommended | |||
|
| ||||||||||
|
|
|
| derating of heaters. | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
*7” W.C. for ETS/ETU | **12” W.C. for ETS/ETU |