System Connectors
Low Voltage connections to signal fault contacts, transfer switch communication and auxiliary 12VDC power are made via a field connection terminal block in control board area. Compare this illustration with your generator to familiarize yourself with the location of these connections.
A- two Pin Terminal Block — Used to connect utility 240 VAC from fuse block in ATS to the control board. Connect only one wire per terminal.
B- fault Contacts — Use NO, COM and NC to hook up a siren, light, etc. to alert you in case of a fault. Contacts reverse state (NO goes to NC
and vice versa) upon a fault condition.
C– Transfer Switch Communication (TxRx and
| TxRx GND) — Connect to transfer switch |
|
|
|
|
|
|
| control board for communication interface |
|
|
|
|
| |
| using 18AWG twisted pair wire. |
|
|
| A |
|
|
D | – +LED and GND Connection — Not required for |
|
|
|
|
| |
| wireless monitor included with unit. Available | 1 | 2 |
|
|
| |
| panel accessory, #6154. | REPRODUCTION |
| ||||
|
| UTILITY | UTILITY | ] | |||
| for optional hardwired remote system status |
|
| . | COM | .C. | |
|
|
|
|
| . |
|
|
E | - eight Pin Terminal Block — Used to connect |
|
|
|
|
| |
| signal wires to the control board. Connect only |
|
|
| B |
| |
| one wire per terminal. |
|
|
|
|
|
|
F | - Power Connection (Line 1 and Line 2) — Power |
|
|
|
|
| |
| NOT |
|
|
|
|
|
|
| connection to transfer switch. |
|
|
|
|
| GND |
G | - neutral and Ground Connection — Connect to |
|
|
|
|
| |
| transfer switch neutral and ground |
|
|
|
|
|
|
| for |
|
|
|
|
|
|
|
|
| E |
TxRx | TxRxGND | +LEDGNDN/C |
|
] ] |
| ||
C |
| D |
|
|
| GROUND] | G |
LINE 1 | ] |
|
LINE 2 | F |
G
NEUTRAL
•For power output connection (Line 1, Line 2, Neutral, and Ground), 300V, 10 AWG copper wire, or 300V, 8 AWG aluminum wire, (ref. NEC Table 310.16, 100 ft. Use National Electric Code for correction factors and wire size calculations).
•For utility circuit connection (Utility A and Utility B) use #14 AWG minimum 300 volt wire.
•For transfer switch communication use #18 AWG twisted pair conductors, no greater than 200 ft in length, 300 volt wire.
•When connecting to the terminal block, fasten only one wire to each connector screw.
•Torque terminal block screws to 4.4
•Torque circuit breaker connections to 45
25