GEK-45404
7
50 - Cycle Burdens at Rated Voltages
RELAY
TYPES VOLTAGE
RATING TAP**SETTING VOLT-AMPS POWER
FACTOR WATTS
IAV51D 345 A(28) 31.9 0.36 11.4
B(42) 28.3 0.56 15.8
C(70) 21.0 0.79 16.6
D(112) 12.8 0.93 11.9
IAV51K 67 A(5.4) 28.8 0.29 8.4
IAV52K B(7.5) 26.6 0.45 12.1
C(12.5) 21.1 0.71 14.9
D(20) 16.0 0.86 13.7
115 No Taps 25.0 0.41 10.1
IAV52C 199 No Taps 25.4 0.28 7.0
345 No Taps 31.9 0.36 11.4
**Minimum pickup volts
TABLE IIIB
60 - Cycle Burden at Rated Voltages
RELAY
TYPES VOLTAGE
RATINGS TAP**SETTINGS VOLT-AMPS POWER
FACTOR WATTS
1AV51D 115 A(10) 0.46 0.99 0.46
B(15) 0.62 1.0 0.62
C(25) 0.96 1.0 0.96
D(40) 1.48 1.0 1.48
IAV51D 199 A(16) 0.41 0.94 0.38
IAV52D B(24) 0.56 0.98 0.55
C(40) 0.89 0.99 0.88
D(64) 1.38 1.0 1.37
IAV51D 345 A(28) 0.48 0.86 0.41
B(42) 0.66 0.95 0.62
C(70) 1.02 0.98 1.01
D(112) 1.4 0.99 1.4
IAV51K 67 A(5.4) 0.43 0.91 0.39
IAV52K B(7.5) 0.57 0.96 0.55
C(12.5) 0.92 0.98 0.91
D(20) 1.47 0.99 1.46
115 No Taps 0.36 0.78 0.28
IAV52C 199 No Taps 0.41 0.94 0.38
345 No Taps 0.48 0.86 0.41
TABLE IIIB