1 |
Participant Participant
Termination
Repeater
Connecting
Segments
Participant
Remote
Repeate
Link Segment (No Participants)
Participant |
| Participant | |||
|
|
|
|
|
|
|
|
|
|
|
|
Termination
Branch Segment
|
|
|
| Remote | |
Participant |
| Repeater | |||
|
|
| |||
|
|
|
|
|
|
To additional participants
Figure 1-2. Repeaters and bus termination
Network Connectors
PROFIBUS connections are created with a 9 pin
Pin-out Listing for the PROFIBUS Bus Plug Connector
Pin No. | Signal | Designation |
|
|
|
1 | Shield | Shield / Protective Ground |
2 | M24 | Ground / Common of the 24V output voltage |
3 | Receive data / transmission data plus | |
4 | Control signal for repeaters (direction control) | |
5 | DGND | Data transmission potential (ground to 5V) |
6 | VP | Supply voltage of the terminating resistance (+ 5V) |
7 | P24 | Output voltage (+ 24V) |
8 | Receive data / transmission data negative | |
9 | Control signal for repeaters (direction control) |
Note: For information on network segment length, network connectors and network termination, and network baud rate, refer to Chapter 2, “Installation.”
Chapter 1 Overview and Specifications |