SCA1001HSS – Advantium® 120 Above-the-Cooktop Oven

Hood Exhaust Duct

Outside ventilation requires a HOOD EXHAUST DUCT. Read the following carefully.

EXHAUST CONNECTION:

The hood exhaust has been designed to mate with a standard 3-1/4” x 10” rectangular duct.

If a round duct is required, a rectangular-to-round transition adaptor must be used. Do not use less than a 6” diameter duct.

REAR EXHAUST:

If a rear or horizontal exhaust is to be used, care should be taken to align exhaust with the space between studs, or wall should be prepared at the time it is constructed by leaving enough space between the wall studs to accommodate exhaust.

MAXIMUM DUCT LENGTH:

For satisfactory air movement, the total duct length of 3-1/4” x 10” rectangular or 6” diameter round duct should not exceed

140 equivalent feet.

ELBOWS, TRANSITIONS, WALL AND ROOF CAPS, etc., present additional resistance to airflow and are equivalent to a section of straight duct which is longer than their actual physical size. When calculating the total duct length, add the equivalent length of all transitions and adaptors plus the length of all straight duct sections. The chart below shows the approximate feet of equivalent length of some typical ducts.

Duct

Equivalent

A. Rectangular-To-Round

5 Ft.

Filter Kit Accessory

Grille

Filter Kit

JX81A–Recirculating Charcoal Filter Kit

To be used when the Advantium oven cannot be vented to the outside.

 

Transition Adaptor

 

 

B. Wall Cap

40

Ft.

C. 90° Elbow

10

Ft.

D. 45° Elbow

5

Ft.

E. 90° Elbow

25

Ft.

F.

45° Elbow

5

Ft.

G.

Roof Cap

24

Ft.

For answers to your Monogram,® GE Profileor GE® appliance questions, visit our website at GEAppliances.com or call

Specification Revised 4/04

GE Answer Center® service, 800.626.2000.

240436

Page 2
Image 2
GE SCA1001HSS dimensions Hood Exhaust Duct, Filter Kit Accessory, Exhaust Connection, Rear Exhaust, Maximum Duct Length