Section 4 — Maintenance

Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators

 

 

CHANGING ENGINE OIL

Figure 4.4 – Engine Air Cleaner

 

 

 

 

 

 

Refer to maintenance performed by authorized service facilities for engine oil and filter change frequencies.

Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:

1.Remove OIL DRAIN HOSE from its retaining clip.

2.Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container.

3.When all oil has drained, install and tighten OIL DRAIN HOSE CAP, and re-install into its retaining clip.

4.Turn OIL FILTER (Figure 4.3) counterclockwise and remove. Dispose of old filter.

See the “Service Schedule,” Section 6, for air cleaner maintenance.

Figure 4.3 - Oil Filter

SPARK PLUGS

OIL FILTER

5.Apply light coating of new engine oil to seal of new oil filter. Install FILTER and tighten by hand only.

DO NOT OVERTIGHTEN.

6.Remove OIL FILL CAP. Add recommended oil (see

SPECIFICATIONS). DO NOT FILL ABOVE THE DIP- STICK “FULL” MARK. Crankcase oil capacity is 4.0 U.S. quarts (3.8 liters).

After refilling the crankcase with oil, always check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK.

7. Start engine and check for oil leaks.

CHANGING THE ENGINE AIR CLEANER

To replace the engine air cleaner, (part number 59402), simply remove the air cleaner cover and replace the air filter making sure it is positioned properly before reat- taching the cover (Figure 4.4).

Reset the spark plug gap or replace the spark plugs as necessary. See Section 6.

1.Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and com- mercial solvent. Do not blast the spark plugs to clean.

2.Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is ques- tionable. See the “Service Schedule,” Section 6, for recommended inspection.

3.Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.5-0.6 mm (0.020-0.025 inch) by carefully bending the ground electrode (Figure 4.5).

Figure 4.5 – Setting the Spark Plug Gap

SET PLUG GAP AT 0.5-0.6 mm

(0.020-0.025 inch)

COOLANT CHANGE

Every year, have Authorized Service Facility drain, flush and refill the cooling system. See SPECIFICATIONS (page 8) for cooling system recommendations.

16 Generac® Power Systems, Inc.

Page 18
Image 18
Generac 004188-1, 004475-1, 004371-2, 004474-1, 004370-2, 004189-1 owner manual Changing the Engine AIR Cleaner, Coolant Change

004371-2, 004188-1, 004474-1, 004475-1, 004370-2 specifications

Generac Power Systems is renowned for its commitment to providing reliable power solutions, and their various models, including the Generac 004189-1, 004370-2, 004475-1, 004474-1, and 004188-1, showcase the company’s innovative engineering and technology. Each of these models is designed to meet diverse energy needs, ensuring homeowners and businesses can maintain power during outages or in remote locations.

The Generac 004189-1 is an essential model in the lineup known for its robust construction and user-friendly interface. It features a powerful engine, ensuring reliable power output and efficient fuel consumption. Additionally, its lightweight design makes it portable, allowing easy relocation to different sites. The model integrates advanced technology for automatic voltage regulation, safeguarding sensitive electronics while operating.

Moving on to the Generac 004370-2, this model emphasizes advanced start-up technology. It is equipped with a reliable electric start feature, minimizing the effort required to power up the generator. Its noise-dampening design significantly reduces sound levels, making it ideal for residential use without causing disturbances to neighbors. The unit also includes a durable metal enclosure that helps protect the generator from the elements and increases its lifespan.

The Generac 004475-1 model stands out for its enhanced fuel efficiency and low emissions. This eco-friendly design adheres to strict emissions regulations, making it a suitable choice for environmentally conscious users. Its intuitive control panel provides easy monitoring of power output, fuel levels, and maintenance needs, ensuring users can efficiently manage their energy requirements.

Similarly, the Generac 004474-1 exemplifies convenience and performance with its dual fuel capability, allowing it to operate on both gasoline and propane. This flexibility ensures users can easily switch fuels based on availability and cost-effectiveness. The model also boasts an extended runtime, capable of powering essential appliances and systems for prolonged periods during outages.

Finally, the Generac 004188-1 emphasizes ease of use, featuring a comprehensive user manual and a straightforward assembly process. The model provides ample power capacity, making it excellent for both emergency back-up and recreational activities. Its compact design allows storage in confined spaces, while its efficient cooling system prevents overheating during extended use.

Overall, these Generac models reflect the company's dedication to innovation, quality, and user satisfaction. With features aimed at enhancing convenience, performance, and environmental responsibility, they cater to the varying power demands of modern users.