Section 2 — Post Installation Start-up and Adjustments

Air-cooled 8.5 kW Generator

2.4GENERATOR TESTS UNDER LOAD

To test the generator set with electrical loads applied, proceed as follows:

1.Set generator’s main circuit breaker to its OFF (or open) position.

2.Turn OFF all loads connected to the transfer switch terminals T1 and T2.

3.Set the generator's AUTO/OFF/MANUAL switch to OFF.

4.Turn OFF the UTILITY power supply to the trans- fer switch, using the means provided (such as a utility main line circuit breaker).

DANGER

Do not attempt manual transfer switch opera- tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.

5.Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator's E1/E2 terminals. The transfer switch operating lever should be down.

6.Set the generator's AUTO/OFF/MANUAL switch to MANUAL. The engine should crank and start immediately.

7.Let the engine stabilize and warm up for a few minutes.

8.Set the generator’s main circuit breaker to its ON (or closed) position. Loads are now powered by the standby generator.

9.Turn ON electrical loads connected to transfer switch terminals T1 and T2. Apply an electrical load equal to the full rated wattage/amperage capacity of the installed generator.

10.Connect an accurate AC voltmeter and a frequen- cy meter across terminal lugs E1 and E2. Voltage should be greater than 230 volts; frequency should be greater than 58 Hertz.

11.Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc.

12.When testing under load is complete, turn OFF electrical loads.

13.Set the generator's main circuit breaker to its OFF (or open) position.

14.Let the engine run at no-load for a few minutes.

15.Set the AUTO/OFF/MANUAL switch to OFF. The engine should shut down.

2.5CHECKING AUTOMATIC

OPERATION

To check the system for proper automatic operation, proceed as follows:

1.Check that the AUTO/OFF/MANUAL switch is set to OFF.

2.Turn OFF the UTILITY power supply to the trans- fer switch, using the means provided (such as a UTILITY main line circuit breaker).

3.Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to the UTILITY power source side.

4.Turn ON the UTILITY power supply to the trans- fer switch, using the means provided (such as a UTILITY main line circuit breaker).

5.Set the AUTO/OFF/MANUAL switch to AUTO. The system is now ready for automatic operation.

6.Turn OFF the UTILITY power supply to the trans- fer switch.

With the AUTO/OFF/MANUAL switch at AUTO, the engine should crank and start when the utility source power is turned OFF. After starting, the transfer switch should connect load circuits to the standby side. Let the system go through its entire automatic sequence of operation.

With the generator running and loads powered by generator AC output, turn ON the UTILITY power supply to the transfer switch. The following should occur:

After about six seconds, the switch should transfer loads back to the UTILITY power source.

About one minute after retransfer, the engine should shut down.

2.6ADJUSTING THE REGULATOR

(NATURAL GAS ONLY)

Although the generator has been factory set to pro- vide maximum power, it may be necessary in some areas to adjust this setting. Because natural gas has different BTU or power content across the country the engine may not perform as designed.

If experiencing engine problems at high or full load conditions follow these steps. It will require a fre- quency meter to perform this procedure.

1.Turn off UTILITY power to the main distribution panel in the house. This can be done by switching the service main breaker to the off or open posi- tion.

2.Allow the generator to start. Before loading the generator, confirm that the no load frequency ,with the roof open and door off, is set at 63-63.5 Hz. Transfer load to emergency circuits.

Generac® Power Systems, Inc. 11

Page 13
Image 13
Generac 004692-2 Generator Tests Under Load, Checking Automatic Operation, Adjusting the Regulator Natural GAS only

004692-2 specifications

The Generac 004692-2 is a reliable and efficient portable generator designed to provide power when and where it’s needed most. Ideal for both residential use and outdoor activities, this generator has become a popular choice for homeowners and outdoor enthusiasts alike.

One of the standout features of the Generac 004692-2 is its power output. It offers a robust wattage capacity, allowing users to run essential appliances during a power outage, or to provide electricity for tools and equipment while camping or during a construction project. Its powerful engine is engineered for durability, ensuring longevity and consistent performance.

Another important aspect of the 004692-2 is its portability. Designed with an ergonomic handle and sturdy wheels, this generator is easy to transport, whether moving it around the yard or taking it on the go for outdoor adventures. Its compact design allows for easy storage, making it a convenient addition to any household.

The Generac 004692-2 incorporates advanced technologies for ease of use and efficiency. It features a user-friendly control panel that includes multiple outlets, allowing users to connect various devices simultaneously. The generator is equipped with a low-oil automatic shutdown system that helps protect the engine from damage, extending the life of the generator.

Moreover, the generator is designed with a quiet operation feature, making it suitable for residential areas. This means users can rely on it for power without disturbing neighbors during critical times such as family gatherings or late-night emergencies.

In terms of fuel efficiency, the Generac 004692-2 performs admirably with its optimized engine design, allowing users to maximize run time while minimizing fuel consumption. This feature is not only cost-effective but also environmentally friendly, reducing the carbon footprint during usage.

Safety is paramount with any generator, and the Generac 004692-2 includes several built-in safety features. The generator is designed to withstand various weather conditions, ensuring reliability during storms or outdoor events. Additionally, the generator's design includes features that reduce the risk of accidental starting, adding an extra layer of protection for the user.

In conclusion, the Generac 004692-2 stands out as an excellent choice for those seeking a dependable portable generator. Its combination of powerful performance, portability, user-friendly design, and built-in safety features makes it an ideal solution for a variety of power needs. Whether for home backup or outdoor use, this generator provides peace of mind with its reliability and efficiency.