Generac Portable Products PP5000T Generator

Ensure a minimum of two feet clearance between open side of box and nearest object.

Face exposed end away from wind and elements.

Enclosure should hold enough heat created by the generator to prevent icing problems.

CAUTION: NEVER run unit indoors; Do not enclose generator any more than shown. Remove shelter when temperatures are above 40°F [4°C].

RECEPTACLES

120 Volt, 20 Amp Duplex Receptacle

Each of these receptacles is protected against overload by a 20 Amp push-to-reset type circuit breakers. Use each receptacle to operate 120 Volt AC, 20 Amp, 60 Hz, single phase loads (Figure 7).

Figure 7 — 120 Volt, 20 Amp Receptacle

Figure 8 — 120/240 Volt, 20 Amp Locking Receptacle

120 Volt, 30 Amp Locking Receptacle

Use a NEMA L5-30P type plug with this receptacle. Connect a 3-wire cord set rated for 125 Volts at 30 Amps to the plug (Figure 9).

Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3600 watts

(3.6 kW) of power at 30 Amps. The outlet is protected by a 30 Amp push-to-reset circuit breaker.

Figure 9 — 120 Volt, 30 Amp Locking Receptacle

120/240 Volt, 20 Amp Locking

Receptacle

Use a NEMA L14-20P type plug with this receptacle. Connect a 4-wire cord set rated for 250 Volts at

20 Amps (or greater) (Figure 8).

You can use the same 4-wire cord if you plan only to run a 120 Volt load. This receptacle powers 120 or 240 Volt AC, 60 Hz, single phase loads and is protected by a 20 Amp push-to-reset circuit breaker.

8

Page 8
Image 8
Generac 11400 manual Receptacles, Volt, 20 Amp Duplex Receptacle, Volt, 30 Amp Locking Receptacle