Specifications
SPECIFICATIONS
STANDBY EMERGENCY GENERATOR
Type...................................................................... | Synchronous |
Rotor Insulation............................................................. | Class H |
Stator Insulation............................................................ | Class H |
Alternator Output Leads | |
Bearings .................................................................. | Sealed Ball |
Coupling ................................................................ | Flexible Disc |
Load Capacity (Standby Rating) ............................... | 25/30 kW* |
*NOTE: Generator rating and performance in accordance with
Excitation System ............................................................ |
| Direct | |
Generator Output Voltage/kW - 60 Hz |
|
| |
| kW | Amp | CB Size |
120/240V, | 25/30 | 104/125 | 125/150 |
120/208V, | 25/30 | 87/104 | 100/125 |
120/240V, | 25/30 | 75/90 | 90/100 |
Generator Locked Rotor KVA Available @ Voltage Dip of 35% | |||
25kW |
| 30kW |
|
35 KVA |
| 45 KVA |
|
ENGINE |
|
|
|
Make ........................................................................... |
| Generac | |
Model ............................................................................. |
| In Line | |
Cylinders and Arrangement ..................................................... |
| 4 | |
Displacement............................................................... |
| 1.6 Liter | |
Bore.............................................................................. |
| 3.15 in. | |
Stroke........................................................................... |
| 3.13 in. | |
Compression Ratio....................................................... |
| ||
Air Intake System......................................... | Naturally Aspirated | ||
Valve Seats ............................................................ |
| Replaceable | |
Lifter Type.................................................................. |
| Hydraulic | |
Spark Plug Gap........................................ | 0.76mm (0.030 inch) | ||
Engine Parameters |
|
|
|
Rated Synchronous RPM ....................................... |
| 60 Hz, 3600 | |
Exhaust System |
|
|
|
Exhaust Flow at Rated Output 60 Hz: | 25kW | 30kW | |
|
| 240 cfm | 260 cfm |
Exhaust Temp. at Rated Output: | 975°F | 1025°F | |
Combustion Air Requirements (Natural Gas) |
| ||
Flow at rated power, 60 Hz: |
| 25kW | 30kW |
|
| 90 cfm | 95 cfm |
Governor |
|
|
|
Type........................................................................... |
| Electronic | |
Frequency Regulation............................................. |
| Isochronous | |
Steady State Regulation ................................................ |
| ± .25% | |
Adjustments: |
|
|
|
Speed..................................................................... |
| Selectable |
Engine Lubrication System |
|
Type of Oil Pump ............................................................... | Gear |
Oil Filter ....................................................... | Full Flow, Cartridge |
Crankcase Oil Capacity ............................................ | 4 U.S. qts. |
COOLING SYSTEM
Type............................................................................... | Closed |
Water Pump............................................................. | Belt Driven |
Fan Speed......................................................................... | 2484 |
Fan Diameter........................................................... | 17.7 inches |
Fan Mode....................................................................... | Pusher |
Air Flow (inlet air including alternator and |
|
combustion air) .................................................. | 1800 ft3/min. |
Coolant Capacity.................................................... | 2.0 U.S. gal. |
Heat Rejection to Coolant (25/35kW) ....112,000/135,000 Btu/h
Maximum Operating Air Temp. on Radiator......... | 60° C (150° F) |
Maximum Ambient Temperature ......................... | 50° C (140° F) |
FUEL SYSTEM
Type of Fuel .................................... | Natural Gas, Propane Vapor | ||||
Carburetor............................................................... |
|
| Down Draft | ||
Secondary Fuel Regulator............................................ |
| Standard | |||
Fuel |
|
| Standard | ||
Operating Fuel Pressure | ................. | 5 in. - 14 in. Water Column | |||
Fuel Consumption - ft3/hr (Natural Gas/LPV) |
| ||||
| Exercise | 25% | 50% | 75% | 100% |
| Cycle | Load | Load | Load | Load |
25kW | 60/24 | 120/48 | 220/87 | 310/123 | 390/155 |
30kW | 60/24 | 145/58 | 260/103 | 370/147 | 470/187 |
ELECTRICAL SYSTEM |
|
|
| ||
Battery Charge Alternator ...................................... | 12V, 15 Amp | ||||
Static Battery Charger ....................................... |
| 2.0 or 2.5 Amp | |||
Recommended Battery................................. |
| Group 26, 525CCA | |||
System Voltage............................................................ |
|
| 12 Volts | ||
Voltage Regulator |
|
|
|
| |
Type........................................................................... |
|
|
| Electronic | |
Sensing ................................................................ |
|
| |||
Regulation........................................................................ |
|
|
| ± 1% | |
Features......................... | Adjustable Voltage and Automatic Gain | ||||
Power Adjustment for Ambient Conditions |
| ||||
Temperature Deration: |
|
|
|
| |
3% for every 10° C above °C | 25kW | 30kW |
| ||
|
|
| 40 | 25 |
|
1.65% for every 10° above °F | 104 | 77 |
| ||
Altitude Deration: |
|
|
|
| |
1% for every 100 m above m | 25kW | 30kW |
| ||
|
|
| 915 | 182 |
|
3% for every 1000 ft. above ft. | 2000 | 600 |
| ||
Controller | ................................................................. |
|
| Nexus |
GenSpec082.RevC12/11