Section 3 - Operation
QUIETSOURCE™ 40kW
•The control board WILL monitor all engine condi- tions and shut down on all the faults listed in this document.
Pos2 OFF — Prepackaged ATS Application
•The control board will perform all of the automat- ic features listed in this document.
•The
GTS Mode Operation
When in GTS mode, the control board will respond as follows based on the AUTO/OFF/MANUAL switch position.
OFF — The generator will not start and run in this position.
MANUAL — The control board will start and run the generator whenever the switch is in the manual posi- tion.
AUTO — The control board will monitor the
NOTE:
If the generator is installed in conjunction with an engineered GTS type transfer switch, refer to the applicable transfer switch manual for exact oper- ating parameters and timing sequences.
3.2CONTROL CONSOLE
COMPONENTS
The components of a home standby generator control console (Figure 3.1) are as follows:
Figure 3.1 - Home Standby Generator Panel
3.2.1 AUTO/OFF/MANUAL SWITCH
Use this
•Set the switch to AUTO for fully automatic opera- tion. See “Automatic Operation” (Section 3.5).
•Set switch to MANUAL position to crank and start the generator engine.
•Set switch to OFF position to shut down an oper- ating engine. With OFF selected, operation will not be possible.
DANGER
With switch set to AUTO, engine can crank and
!start suddenly without warning. Such automat- ic start up normally occurs when utility source voltage drops below a
3.2.2 FAULT INDICATOR LED
This LED goes ON when one or more of the following engine faults occurs and when engine shuts down.
•Low Oil Pressure
•Overcrank
•Low Battery
•Overspeed/RPM Sensor Loss
•High Coolant Temperature/Low Coolant Level
See Section 1.7 for further explanation of engine pro- tection functions.
3.2.3 15 AMP FUSE
This fuse protects the control console’s DC control circuit against electrical overload. If the fuse has melted open because of an overload, engine cranking and startup cannot occur. If the fuse needs to be replaced, use only an identical
SET EXECISER TIME SWITCH
LED INDICATORS:
FLASHING GREEN LED = NO UTILITY SENSE
5 FLASHING RED LED'S = EXERCISER NOT SET
(IN AUTO MODE ONLY) SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON RED LED'S = INDIVIDUAL FAULT
(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)
| OVER CRANK | RED LEDs |
|
| |
4A | LOW BATTERY |
|
| SYSTEM READY |
|
| AUTO |
|
OFF |
|
|
| OFF |
|
ON |
|
|
SET | MANUAL | GREEN LED |
EXERCISE | TO SET EXERCISER TIME |
TIME
1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.
0E7194
fuse. (Type AGC)
3.2.4 4.0 AMP INLINE FUSE
This fuse protects the battery charger against electri- cal overload. If the fuse needs to be replaced, use only an identical
NOTE:
This fuse will not remove the + battery input power from the PCB when it opens. This means the exercise timer will not be reset.
| AUTO/OFF/MANUAL |
4A FUSE | SWITCH |
| |
BATTERY | 15A FUSE |
CHARGER | MAIN |
| POWER |
3.2.5 SET EXERCISE TIME SWITCH
This switch allows programming the generator to start and exercise automatically. “See Weekly Exercise Cycle.”
Generac® Power Systems, Inc. 13