Generac GR160 manual Operating Data

Models: GR160

1 4
Download 4 pages 56.98 Kb
Page 3
Image 3
OPERATING DATA

GR160

OPERATING DATA

 

 

 

 

 

 

STANDBY

 

 

PRIME

 

 

 

 

 

 

 

GR160

 

 

GR160

 

GENERATOR OUTPUT VOLTAGE/KW-60HzSTANDBY

 

 

 

 

 

 

 

 

240V, 1-phase, 1.0 pf

 

kW

 

133

 

 

 

126

 

120/208V, 3-phase, 0.8 pf

 

kW

 

133

 

 

 

126

 

139/240V, 3-phase, 0.8 pf

 

kW

 

133

 

 

 

126

 

277/480V, 3-phase, 0.8 pf

 

kW

 

133

 

 

 

126

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AMPERAGE

 

 

 

 

 

 

 

 

 

 

 

 

Single phase 240V

 

 

Amps

 

554

 

 

 

525

 

Three phase 208V

 

 

 

Amps

 

461

 

 

 

437

 

Three phase 240V

 

 

 

Amps

 

400

 

 

 

379

 

Three phase 480V

 

 

 

Amps

 

200

 

 

 

189

 

 

 

 

 

 

 

 

MOTOR STARTING KVA

 

 

416V

480V

416V

480V

Maximum at 35% instantaneous voltage dip

60 Hz - kVA

680

 

950

 

680

950

 

 

 

 

 

 

 

 

 

 

 

 

 

FUEL

 

 

 

 

 

 

 

 

 

 

 

 

Fuel consumption 60 Hz

 

Load

25%

50%

75%

100%

25%

50%

75% 100%

 

 

 

 

gal/hr

4.4

6.6

8.8

9.3

3.5

5.3

7.0

7.4

 

 

 

 

liters/hr

16.7

25.0

33.3

35.2

13.4

20.0

26.6

28.2

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING

 

 

 

 

 

 

 

 

 

 

 

 

Coolant capacity

 

 

System lit (US gal)

 

22 (5.8)

 

 

22 (5.8)

 

 

 

 

Engine lit (US gal)

 

14 (3.7)

 

 

14 (3.7)

 

 

 

 

Radiator lit (US gal)

 

8 (2.1)

 

 

8 (2.1)

 

Coolant flow/min.

 

 

60 Hz - lit (US gal)

 

270 (71.3)

 

 

270 (71.3)

 

Heat rejection to coolant

 

BTU/hr

 

344,000

 

 

309,600

 

Inlet air

 

60 Hz - cu meters/min (cfm)

 

120 (4500)

 

 

120 (4500)

 

Max. inlet air temperature

 

°F

 

110

 

 

 

 

110

 

 

 

 

 

 

 

 

 

 

 

COMBUSTION AIR REQUIREMENTS

 

 

 

 

 

 

 

 

 

Flow at rated power

60 Hz - cu meters/min (cfm)

 

8.9 (314)

 

 

8.0 (283)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXHAUST

 

 

 

 

 

 

 

 

 

 

 

 

Exhaust flow at rated output 60 Hz cu meters/min (cfm)

 

31.6 (1115)

 

 

28.4 (1003)

 

Maximum recommended back pressure

Kpa ("H2O)

 

7.5 (30)

 

 

7.5 (30)

 

Exhaust temperature at rated output

°C (°F)

 

496 (925)

 

 

446 (835)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENGINE

 

 

 

 

 

 

 

 

 

 

 

 

Rated RPM

 

 

 

60 Hz

 

1800

 

 

1800

 

Rated HP

 

 

 

60 Hz

 

194

 

 

 

175

 

Piston speed

 

 

60 Hz - m/min (ft/min)

 

464 (1524)

 

 

464 (1524)

 

BMEP (psi)

 

 

 

60 Hz

 

171

 

 

 

155

 

 

 

 

 

 

 

 

 

 

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

 

 

 

 

 

 

 

 

Temperature

 

-3% for every 10°C above - °C

 

25

 

 

 

 

25

 

 

 

-1.5% for every 10°F above - °F

 

77

 

 

 

 

77

 

Attitude

-3.0% for every 300 m above - m

 

1523

 

 

1523

 

 

-3.0% for every 1000 ft above - ft

 

5000

 

 

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

 