Generac PP5000T manual Volt, Duplex Receptacles, 120/240 Volt, 20 Amp Locking Receptacle

Models: PP5000T

1 20
Download 20 pages 12.35 Kb
Page 9
Image 9

Generac Portable Products PP5000T Generator

Ensure a minimum of two feet clearance between open side of box and nearest object.

Face exposed end away from wind and elements.

Enclosure should hold enough heat created by the generator to prevent icing.

DANGER! Carbon Monoxide Hazard! Never run unit indoors. Do Not enclose generator any more than shown. Remove shelter when temperatures are above 40°F [4°C].

RECEPTACLES

120 Volt, Duplex Receptacles

Each of these receptacles (Figure 8) are protected against overload by 20 Amp push-to-reset type circuit breakers.

Figure 8 — 120 Volt, 20 Amp Duplex Receptacle

Use each receptacle to operate 120 Volt AC, 60 Hz, single phase loads at 20 Amps of current.

120/240 Volt, 20 Amp Locking Receptacle

Use a NEMA L14-20 plug with this receptacle. Connect a 4-wire cord set rated for 250 Volts at 20 AC Amps (or greater) to the plug (Figure 9). You can use the same 4-wire cord if you plan only to run a 120 Volt load.

Figure 9 — 120/240 Volt, 20 Amp Locking Receptacle

Use this receptacle to operate 120 Volt or 240 Volt AC, 60 Hz, single phase loads at 20 Amps. This outlet is protected by a 20 Amp push-to-reset circuit breaker.

120 Volt, 30 Amp Locking Receptacle

Use a NEMA L5-30 plug with this receptacle. Connect a 3-wire cord set rated for 125 Volts at 30 AC Amps to the plug (Figure 10).

Figure 10 — 120 Volt, 30 Amp Locking Receptacle

Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3,600 watts

(3.6 kW) of power at 30 AC Amps. The outlet is protected by a 30 Amp push-to-reset circuit breaker.

9

Page 9
Image 9
Generac PP5000T Volt, Duplex Receptacles, 120/240 Volt, 20 Amp Locking Receptacle, Volt, 30 Amp Locking Receptacle