Model RTS10EZA1 RTS12EZA1 RTS14EZA1 RTS16EZA1
Voltage 240, 1ø 240, 1ø 240, 1ø 240, 1ø
Circuits***50A, 240V – – – 1
40A, 240V – 1 1 1
30A, 240V 1 1 – –
20A, 240V 1 – 1 1
20A, 120V 3365
15A, 120V 3545
Phase 1
Rated AC Frequency 60 Hz
Enclosure Material Steel
Enclosure Type NEMA 1
Unit Weight (lbs./kilos) 57/25.9 60.8/27.5 64/29 68/30.8
Withstand Rating (Amps) 10,000
Lug Range 2/0 - #14
Load Transition Type Open Transition
Wire Gauge (Hot, Neutral, Ground, Control) 10, 10, 10, 18 8, 8, 10, 18 6, 6, 8, 18 6, 6, 8, 18
FUNCTIONSGenerac EZ Switch™
All Timing and sensing functions originate in the generator controller
Utility voltage drop-out ......................................................................................................................................................................................................................<60%
Timer to generator start ......................................................................................................................................10 second factory set, adjustable between 10-30 seconds
Engine warm up delay .................................................................................................................................................................................................................5 seconds
Standby voltage sensor ..................................................................................................................................................................................................60% for 5 seconds
Utility voltage pickup .........................................................................................................................................................................................................................>80%
Re-transfer time delay ...............................................................................................................................................................................................................15 seconds
Engine cool-down timer ............................................................................................................................................................................................................60 seconds
Exerciser ..............................................................................................................................................................................................................12 minutes every 7 days
The transfer switch can be operated manually without power applied.
SPECIFICATIONS®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2012 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0186640SBY-D / Printed in U.S.A. 02/17/12
EZ Switch™ Features• Electrically operated, mechanically-held contacts for fast, positive connections.
• Rated for all classes of load, 100% equipment rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMA 1 (indoor rated) enclosure is standard on the 100 amp switch.
• 2 Year Limited Warranty
Mechanical Dimensions (in inches/mm)
Current
Rating
No. of
Poles
Height Width Depth
H1 H2 W1 W2
7/177.8100 UL Listed 2 26.5/673.1 29.25/742.9 8.14/206.7 12.5/317.5
Terminal Wire Ranges
ATS Rated Amps Switch Terminal Neutral Lug/Stud Ground Lug
100A 2-Pole UL 1 x 1/0-12 1 x 3/8-16 Stud 1 x 2/0-14
731.9
[28.8]
637.6
[25.1]
LEFT SIDE VIEW
642
[25.3] 76.2 [3.0]
PEA GRAVEL
MINIMUM
TRANSFER
SWITCH
8KW - 17KW
(IF SUPPLIED)
TRANSFER
SWITCH
20KW
(IF SUPPLIED)
1218
[47.9]
FRONT VIEW
1226
[48.3]
H2
H1
W1
W2
H2
H1
W1
W2
®