Section 3 — Operation

ATS “HS” Type Transfer Switch

Connect power source load conductors to clearly marked transfer mechanism terminal lugs as follows

1.Connect UTILITY (NORMAL) power source cables to switch terminals N1, N2.

2.Connect EMERGENCY (STANDBY) source power cables to transfer switch terminals E1, E2.

3.Connect customer LOAD leads to switch termi- nals T1, T2.

Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of the correct wire gauge size in accordance with applicable codes.

Be sure to maintain proper electrical clearance between live metal parts and grounded metal. Allow at least 1/2 inch for 100-400 amp circuits.

2.5CONNECTING START CIRCUIT

WIRES

Control system interconnections (Section 6) consist of UTILITY 1 (N1) and UTILITY 2 (N2), LOAD 1 (T1) and LOAD 2 (T2), and leads 23 and 194 when used in conjunction with some water-cooled generators. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below:

 

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE

 

 

 

SIZE

 

 

460 feet (140m)

No. 18 AWG.

 

 

461 to 730 feet (223m)

No. 16 AWG.

 

 

731 to 1,160 feet (354m)

No. 14 AWG.

 

 

1,161 to 1,850 feet (565m)

No. 12 AWG.

 

 

 

 

 

NOTE:

If there are no matching terminal connections for LOAD 1 (T1) and LOAD 2 (T2) in the generator control panel, do not connect these wires. Failure of the control board will occur if connected.

3.1FUNCTIONAL TESTS AND

ADJUSTMENTS

Following transfer switch installation and inter- connection, inspect the entire installation careful- ly. A competent, qualified electrician should inspect it. The installation should comply strictly with all applicable codes, standards, and regula- tions. When absolutely certain the installation is proper and correct, complete a functional test of the system.

Perform functional tests in the exact order

!presented in this manual, or damage could be done to the switch.

4

IMPORTANT: Before proceeding with functional tests, read and make sure all instructions and infor- mation in this section are understood. Also read the information and instructions of labels and decals affixed to the switch. Note any options or accessories that might be installed and review their operation.

3.2MANUAL OPERATION

DANGER

Do NOT manually transfer under load.

!Disconnect transfer switch from all power sources by approved means, such as a main circuit breaker(s).

A manual HANDLE is shipped with the transfer switch. Manual operation must be checked BEFORE the transfer switch is operated electrically. To check manual operation, proceed as follows:

1.Turn the generator’s AUTO-OFF-MANUAL switch to OFF.

2.Turn OFF both UTILITY and EMERGENCY power supplies to the transfer switch, with what- ever means provided (such as the main line cir- cuit breakers).

3.Note position of transfer mechanism main con- tacts by observing the moveable contact carrier arm.

Manual operation handle towards the top of switch mechanism - LOAD terminals (T1, T2) are connected to UTILITY terminals (N1, N2).

Manual operation handle towards the bottom of switch mechanism - LOAD terminals (T1, T2) are connected to EMERGENCY terminals (E1, E2).

Do not use excessive force when operating

!the transfer switch manually or damage could be done to the manual handle.

3.2.1 CLOSE TO NORMAL SOURCE SIDE

Before proceeding, verify the position of the switch by observing the position of manual operation handle in Figure 3.1. If the handle is UP, the contacts are closed in the NORMAL position, no further action is required. If the handle is DOWN, proceed with Step 1.

Step 1: With the handle inserted into the actuating shaft, move handle UP. Be sure to hold on to the handle as it will move quickly after the center of travel.

Page 6
Image 6
Generac Power Systems 004635-3, 004678-2 Connecting Start Circuit Wires, Functional Tests Adjustments, Manual Operation

004678-2, 004635-3, 004678-2 specifications

Generac Power Systems is a prominent name in the field of backup power generation, renowned for their wide array of innovative products designed to meet diverse energy needs. Among their extensive catalog, the Generac models 004635-3 and 004678-2 stand out, showcasing cutting-edge features and technologies that provide reliable power solutions for both residential and commercial applications.

The Generac 004635-3 is a robust standby generator that operates on a reliable liquid propane or natural gas fuel source. One of its main features is the True Power Technology, which ensures smooth operation of sensitive electronics such as computers and televisions, minimizing the risk of damage during power outages. With its powerful engine and efficient design, this generator can produce substantial wattage to power essential appliances and systems, providing peace of mind during electrical failures.

A notable characteristic of the 004635-3 is its automatic transfer switch that seamlessly detects utility outages and activates the generator within seconds. This quick response time is crucial, as it guarantees that your home remains functional during unexpected power interruptions. Additionally, the model is equipped with a mobile link remote monitoring feature that allows users to track performance and status through an app, ensuring they are always informed about their backup power system.

On the other hand, the Generac 004678-2 also carries the hallmark of high-performance and reliability, making it an excellent choice for larger applications. This model features an innovative, noise-reducing enclosure that not only minimizes sound output but also enhances durability against harsh weather conditions. The generator also boasts a user-friendly control panel with digital display technology, providing a straightforward interface for monitoring and managing the system.

A standout technology in the 004678-2 is the G-Force engine, designed for optimal performance and longevity. This engine emphasizes low-maintenance operation, reducing the frequency of service intervals and ensuring the generator runs efficiently for years. The model's large fuel tank further extends its run time, ensuring users have sufficient power during extended outages.

In summary, both the Generac 004635-3 and 004678-2 models exemplify the company’s commitment to quality and innovation. These generators integrate advanced technology, robust design, and user-friendly features, making them ideal solutions for anyone seeking reliable backup power. With Generac, customers can take comfort in knowing they have a dependable power source at their fingertips in any emergency situation.