Generac Power Systems 005324-0 Maintenance, Standby Generator Sets Service Schedule, Level, Tasks

Models: 005325-0 005324-0

1 60
Download 60 pages 49.04 Kb
Page 22
Image 22
Maintenance

Standby Generator Sets

Service Schedule

Maintenance

Level 1

 

Level 2

 

Level 3

 

Level 4

 

Tasks

Recom-

Task

Required

Task

Required

Task

 

Task

 

mended

Comp.

to be done

Comp.

to be done

Comp.

Required

Comp.

 

to be done

(Date-

3 months/

(Date-

Semi-

(Date-

to be done

(Date-

 

monthly

In itials)

Break-in

Initials)

annually

Initials)

Annually

Initials)

 

10 Hrs.

 

30 Hrs.

 

50 Hrs.

 

100 Hrs.

 

13.Initiate an automatic start and transfer of the unit to

site load and exercise it for at least 1 hour looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary.

14.Start and exercise the unit at full rated load (use a

load bank if the site load is not enough) for at least 2 hours looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary.

15. Change the engine oil.

16.Replace the engine oil filter(s).

17.Replace the engine air filter(s).

18.Replace the engine fuel filter(s) on diesel engine driven units and re-prime the fuel system.

19.Check the engine spark plugs on gas engine driven units. Clean and re-gap or replace as necessary.

20.Perform a 5 minute no-load operational run of the unit looking for any post service problems.

21.Return the unit to standby

setup for operation when required.

11-3

12/05 B .Rev SrvSchd002

Page 22
Image 22
Generac Power Systems 005324-0, 005325-0 owner manual Maintenance, Standby Generator Sets Service Schedule, Level, Tasks