Generac Power Systems 05402 manual Operating Data, STANDBY 30 kW

Models: 05402

1 4
Download 4 pages 15.39 Kb
Page 3
Image 3
OPERATING DATA

STANDBY 30 kW

OPERATING DATA

 

 

 

 

STANDBY 30 kW

 

KW RATING

 

 

 

30 LP / 29 NG

 

 

 

 

 

 

 

ENGINE SIZE

 

 

 

1.6 Liter 4 cyl. inline

 

 

 

 

 

 

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

 

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

 

 

30 LP / 29 NG

125 LP / 120.8 NG

150

 

 

 

 

 

 

GENERATOR LOCKED ROTOR KVA

 

 

 

 

 

AVAILABLE @ VOLTAGE DIP OF 35%

 

single phase

 

56

 

 

 

 

 

 

ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)

 

Natural Gas

 

Propane

 

 

 

(ft3/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

 

 

60

0.65

24

25% of rated load

 

 

193

2.1

76

50% of rated load

 

 

300

3.3

120

75% of rated load

 

 

415

4.5

165

100% of rated load

 

 

525

5.7

209

 

 

 

 

 

 

ENGINE COOLING

 

ft3/min.

 

 

 

Air flow (inlet air including alternator and combustion air)

 

1,800

 

System coolant capacity

 

US gal.

 

2.0

 

Heat rejection to coolant

 

BTU/hr.

 

131,000

 

Max. operating air temp. on radiator

 

°C (°F)

 

60 (150)

 

Max. ambient temperature

 

°C (°F)

 

50 (140)

 

 

 

 

 

 

 

COMBUSTION AIR REQUIREMENTS

 

 

 

 

 

Flow at rated power 60 Hz

 

cfm

 

95

 

 

 

 

 

 

 

SOUND EMISSIONS IN DBA

 

 

 

 

 

db(A) @ 23 feet in exercise mode

 

 

 

62

 

db(A) @ 23 feet at normal operating load

 

 

75

 

 

 

 

 

 

 

EXHAUST

 

 

 

 

 

Exhaust flow at rated output 60 Hz

 

cfm

 

260

 

Exhaust temp. at muffler outlet

 

°F

 

1025

 

 

 

 

 

 

 

ENGINE PARAMETERS

 

 

 

 

 

Rated synchronous RPM

 

60 Hz

 

3600

 

HP at rated KW

 

60 Hz

 

48

 

 

 

 

 

 

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

 

 

 

 

Temperature Deration

3% for every 10 °C above - °C

 

25

 

1.65% for every 10 °F above - °F

 

77

 

Altitude Deration

1% for every 100 m above - m

 

183

 

 

3% for every 1000 ft. above - ft.

 

600

 

 

 

 

 

 

 

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuelBtu content, ambient temperature, altitude, engine power and condition, etc.

Page 3
Image 3
Generac Power Systems 05402 manual Operating Data, STANDBY 30 kW