Generac Power Systems 5466 Specifications, Surface Mount Annunciator, Flush Mount Annunciator

Models: 5466 5464 5465

1 2
Download 2 pages 27.05 Kb
Page 2
Image 2
21 Light Remote Annunciator

21 Light Remote Annunciator

Specifications

Function

Color

 

Alarm

Latched

Pre-Low Oil Pressure

Yellow

n

Yes

Yes

Pre-High Water Temp

Yellow

n

Yes

Yes

Pre Low Water Temp

Yellow

n

Yes

Yes

Pre-Low Fuel

Yellow

n

Yes

Yes

Battery Charge AC Fail

Yellow

n

Yes

No

Low Battery Voltage

Yellow

n

Yes

No

High Battery Voltage

Yellow

n

No

No

Not in Auto

Red

n

Yes

No

RPM Sensor Loss

Red

n

Yes

Yes

Overcrank

Red

n

Yes

Yes

Overspeed

Red

n

Yes

Yes

Low Oil Pressure

Red

n

Yes

Yes

Hi Water Temp

Red

n

Yes

Yes

Low Water Level

Red

n

Yes

Yes

Emergency Stop

Red

n

Yes

No

Gen Running

Yellow

n

No

No

Gen Power (ATS)

Yellow

n

No

No

Line Power (ATS)

Green

n

No

No

Systems Ready

Green

n

Yes

No

Communications OK

Green

n

Yes

No

Spare

Green

n

No

No

Spare Keypad Switch - Can be used to implement a remote start function. (Model 5464 only)

Surface Mount Annunciator

The 21-Light Annunciator can mount to a flat surface with connections through the 0.812 Dia. knockout on the back surface or through 0.812 knockouts on sides as shown.

11.42

10.24

9.06

 

1.64

 

 

5.8

 

 

0.86

 

 

0.812 Dia.

0.812 Dia.

4.53

Both sides

2.32

 

 

1.93

Flush Mount Annunciator

 

7.09

8.27

Four mounting holes for 21 Light Annunciator

4-mm -0.7 Female Thread

￿1.57

Thru

1.21

9.64

Outside

R0.59

Both Sides

Cut

Rough Opening

6.75 " x 9.88 "

6.49

1.42

SpecificationsSurface Mount Annunciator0.87

This Flush Mount Box is recessed into the wall opening and the sur- face mount annunciator mounts to the (4) 4 mm screw holes on the back surface. After wire connec- tions are made the front annuncia- tor cover is attached.

Generac Power Systems, Inc. • P.O. Box 297, Whitewater, WI 53190 • guardiangenerators.com

©2008 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0177350SBY/Printed in U.S.A. 04.08, rev. 05.08

Page 2
Image 2
Generac Power Systems 5466 Specifications, Surface Mount Annunciator, Flush Mount Annunciator, Light Remote Annunciator