Generac Power Systems None manual Operating Data, COMMERCIAL 130 kW

Models: None

1 4
Download 4 pages 42.78 Kb
Page 3
Image 3
OPERATING DATA

COMMERCIAL 130 kW

COMMERCIAL SERIES

OPERATING DATA

 

 

 

COMMERCIAL 130 kW

 

KW RATING

 

 

130

 

 

 

 

 

 

ENGINE SIZE

 

 

6.8 Liter V-10

 

 

 

 

 

 

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

 

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

 

130

541.6

600

120/208V, 3-phase, 0.8 pf

 

130

451.5

500

120/240V, 3-phase, 0.8 pf

 

130

391.3

450

277/480V, 3-phase, 0.8 pf

 

130

195.6

225

 

 

 

 

 

GENERATOR LOCKED ROTOR KVA

 

 

 

 

AVAILABLE @ VOLTAGE DIP OF 35%

 

 

 

 

Single phase or 208V & 240V 3-phase

 

 

270

 

480V 3-phase

 

 

320

 

 

 

 

 

 

ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)

 

Natural Gas

 

Propane

 

 

(ft3/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

 

135

1.48

54.5

25% of rated load

 

482

5.28

194.3

50% of rated load

 

927

10.15

373.5

75% of rated load

 

1292

14.15

520.7

100% of rated load

 

1786

19.56

719.8

 

 

 

 

 

ENGINE COOLING

ft3/hr.

 

 

 

Air flow (inlet air including alternator and combustion air)

 

6,450

 

System coolant capacity

US gal.

 

4.5

 

Heat rejection to coolant

BTU/hr.

 

496,000

 

Max. operating air temp. on radiator

°C (°F)

 

60 (150)

 

Max. ambient temperature

°C (°F)

 

50 (140)

 

 

 

 

 

 

COMBUSTION AIR REQUIREMENTS

 

 

 

 

Flow at rated power 60 Hz

cfm

 

336

 

 

 

 

 

 

SOUND EMISSIONS IN DBA

 

 

 

 

db(A) @ 23 feet in exercise mode

 

 

65

 

db(A) @ 23 feet at normal operating load

 

 

75

 

 

 

 

 

 

EXHAUST

 

 

 

 

Exhaust flow at rated output 60 Hz

cfm

 

1,119

 

Exhaust temp. at muffler outlet

°F

 

970

 

 

 

 

 

 

ENGINE PARAMETERS

 

 

 

 

Rated synchronous RPM

60 Hz

 

3000

 

HP at rated KW

60 Hz

 

210

 

 

 

 

 

 

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

 

 

 

 

Temperature Deration

 

 

 

 

3% for every 10 °C above - °C

 

25

 

1.65% for every 10 °F above - °F

 

77

 

Altitude Deration

 

 

 

 

1% for every 100 m above - m

 

183

 

3% for every 1000 ft. above - ft.

 

600

 

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.