QT022
kW RATING 22
ENGINE SIZE 2.4LiterInline4
GENERATOR OUTPUT VOLTAGE/KW - 60Hz KW AMP CB Size
 120/208V,3-phase,0.8pf 22 76 100
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
 Singlephaseor2083-phase 43
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) Natural GasPropane
(ft3/hr.) (gal/hr.) cuft/hr
 Exercisecycle 42 0.44 16
 25%ofratedload 100 1.0 38
 50%ofratedload 190 2.0 98
 75%ofratedload 255 2.7 98
 100%ofratedload 316 3.3 120
ENGINE COOLING
Airflow(inlet air including alternator and combustion air) ft3/min. 2,400
 Systemcoolantcapacity USgal. 2.5
 Heatrejectiontocoolant BTU/hr. 99,000
 Max.operatingairtemp.onradiator °C(°F) 60(150)
 Max.ambienttemperature °C(°F) 50(140)
COMBUSTION AIR REQUIREMENTS
Flowatratedpower60Hz cfm 68

SOUND EMISSIONS IN DBA
 Exercisingat7meters 61
 Normaloperationat7meters 70
EXHAUST
Exhaustflowatratedoutput60Hzcfm 165
 Exhausttemp.atmuffleroutlet °F 900
ENGINE PARAMETERS
RatedsynchronousRPM 60Hz 1800
 HPatratedKW 60Hz 40
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
 TemperatureDeration
  3%forevery10°Cabove-°C 25
  1.65%forevery10°Fabove-°F 77
 AltitudeDeration
  1%forevery100mabove-m 183
  3%forevery1000ft.above-ft. 600
ENCLOSURE
Material  Aluminum
Color  PMS422(Bisque)
OPERATING DATA

QT022

RATING:Allthreephasesunitsareratedat0.8powerfactor.Allsinglephaseunitsareratedat1.0powerfactor.STANDBYRATING:Standbyratings
applytoinstallationsservedbyareliableutilitysource.Thestandbyratingisapplicabletovaryingloadsforthedurationofapoweroutage.Thereis
nooverloadcapabilityforthisrating.RatingsareinaccordancewithISO-3046-1.Design��andspecificationsare subjecttochangewithoutnotice.