QT027
OPERATING DATA
|
|
|
| QT027 |
|
|
KW RATING |
|
|
| 27 |
|
|
|
|
|
|
| ||
ENGINE SIZE |
|
| 2.4 Liter Inline 4 |
| ||
|
|
|
|
|
|
|
GENERATOR OUTPUT VOLTAGE/KW - 60Hz |
| KW Nat. Gas | AMP | KW LPG | AMP | CB Size (Both) |
120/240V, |
| 25 | 104 | 27 | 112 | 125 |
120/208V, |
| 25 | 87 | 27 | 94 | 100 |
120/240V, |
| 25 | 75 | 27 | 81 | 90 |
|
|
|
|
|
|
|
GENERATOR LOCKED ROTOR KVA |
|
|
|
|
|
|
AVAILABLE @ VOLTAGE DIP OF 35% |
|
|
|
|
|
|
Single phase or 208 |
|
|
| 43 |
|
|
|
|
| ||||
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) | Natural Gas (25 kW) | Propane (27 kW) | ||||
|
| (ft3/hr.) | (gal/hr.) | cu ft/hr | ||
Exercise cycle |
|
| 42 | 0.44 |
| 16 |
25% of rated load |
|
| 108 | 1.2 |
| 44 |
50% of rated load |
|
| 197 | 2.2 |
| 81 |
75% of rated load |
|
| 287 | 3.2 |
| 118 |
100% of rated load |
|
| 359 | 4.1 |
| 147 |
|
|
|
|
|
|
|
ENGINE COOLING |
|
|
|
|
|
|
Air flow (inlet air including alternator and combustion air) | ft3/min. |
|
| 2,400 |
|
|
System coolant capacity | US gal. |
|
| 2.5 |
|
|
Heat rejection to coolant | BTU/hr. |
|
| 120,000 |
|
|
Max. operating air temp. on radiator | °C (°F) |
|
| 60 (150) |
|
|
Max. ambient temperature | °C (°F) |
|
| 50 (140) |
|
|
|
|
|
|
|
|
|
COMBUSTION AIR REQUIREMENTS |
|
|
|
|
|
|
Flow at rated power 60 Hz | cfm |
|
| 68 |
|
|
|
|
|
|
|
|
|
SOUND EMISSIONS IN DBA |
|
|
|
|
|
|
Exercising at 7 meters |
|
|
| 62 |
|
|
Normal operation at 7 meters |
|
|
| 75 |
|
|
|
|
|
|
|
|
|
EXHAUST |
|
|
|
|
|
|
Exhaust flow at rated output 60 Hz | cfm |
|
| 130 |
|
|
Exhaust temp. at muffler outlet | °F |
|
| 900 |
|
|
|
|
|
|
|
|
|
ENGINE PARAMETERS |
|
|
|
|
|
|
Rated synchronous RPM | 60 Hz |
|
| 1800 |
|
|
HP at rated KW | 60 Hz |
|
| 40 |
|
|
|
|
|
|
|
| |
POWER ADJUSTMENT FOR AMBIENT CONDITIONS |
|
|
|
|
| |
Temperature Deration |
|
|
|
|
|
|
3% for every 10 °C above - °C |
|
| 25 |
|
| |
1.65% for every 10 °F above - °F |
|
| 77 |
|
| |
Altitude Deration |
|
|
|
|
|
|
1% for every 100 m above - m |
|
| 183 |
|
| |
3% for every 1000 ft. above - ft. |
|
| 600 |
|
| |
|
|
|
|
|
|
|
ENCLOSURE |
|
|
|
|
|
|
Material |
|
|
| Aluminum |
|
|
Color |
|
| PMS 422 (Bisque) |
| ||
|
|
|
|
|
|
|
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with