Product Specifications
Specifications (cont.)
GPG1348
090M41A
GPG1348
115M41A
GPG1360
090M41A
GPG1360
115M41A
GPG1360
140M41A
Cooling Capacity
Total BTU/h | 46,000 | 46,000 | 57,000 | 57,000 | 57,000 |
Sensible BTU/h | 36,700 | 36,700 | 43,800 | 43,800 | 43,800 |
SEER / EER | 13.0 / 11.0 | 13.0 / 11.0 | 13.0 / 10.75 | 13.0 / 10.75 | 13.0 / 10.75 |
Decibels | 80 | 80 | 80 | 80 | 80 |
AHRI Reference #s | 4385097 | 4385097 | 4385099 | 4385099 | 4385099 |
Heating Capacity |
|
|
|
|
|
Input BTU/h | 92,000 | 115,000 | 92,000 | 115,000 | 138,000 |
|
|
|
|
|
|
Output BTU/h | 73,600 | 92,000 | 73,600 | 92,000 | 110,400 |
|
|
|
|
|
|
AFUE | 80 | 80 | 80 | 80 | 80 |
|
|
|
|
|
|
Temperature Rise Range | 45 - 75 | 45 - 75 | 45 - 75 | 45 - 75 | 45 - 75 |
|
|
|
|
|
|
No. of Burners | 4 | 5 | 4 | 5 | 6 |
|
|
|
|
|
|
Orifice Size (Natural/Propane) | 43 / 55 | 43 / 55 | 43 / 55 | 43 / 55 | 43 / 55 |
|
|
|
|
|
|
Evaporator Motor |
|
|
|
|
|
Type | EEM | EEM | EEM | EEM | EEM |
Wheel (D x W) | 11” x 10” | 11” x 10” | 11” x 10” | 11” x 10” | 11” x 10” |
Indoor Nominal CFM | 1,550 | 1,550 | 1,750 | 1,750 | 1,750 |
Motor Speed Tap (Cooling) | T4 | T4 | T4 | T4 | T4 |
RPM/Amps (Cooling) | 1,050/5.8 | 1,050/5.8 | 1,050/7.6 | 1,050/7.6 | 1,050/7.6 |
Horsepower | 3/4 | 3/4 | 1.0 | 1.0 | 1.0 |
Evaporator Coil |
|
|
|
|
|
|
|
|
|
|
|
Face Area (ft²) | 5.67 | 5.67 | 5.67 | 5.67 | 5.67 |
|
|
|
|
|
|
Rows Deep/Fins per Inch | 4/14 | 4/14 | 4/14 | 4/14 | 4/14 |
|
|
|
|
|
|
Piston Size (Cooling) | 0.076 | 0.076 | 0.087 | 0.087 | 0.087 |
|
|
|
|
|
|
Filter Size (ft²) | 5.1 | 5.1 | 6.3 | 6.3 | 6.3 |
|
|
|
|
|
|
Drain Size (NPT) | ¾” | ¾” | ¾” | ¾” | ¾” |
Refrigerant Charge (oz.) | 125 | 125 | 185 | 185 | 185 |
Condenser Fan / Coil |
|
|
|
|
|
Horsepower - RPM | 1/4 - 1100 | 1/4 - 1100 | 1/4 - 1100 | 1/4 - 1100 | 1/4 - 1100 |
Diameter / # of Blades | 22” / 3 | 22” / 3 | 22” / 3 | 22” / 3 | 22” / 3 |
Outdoor Nominal CFM | 3,500 | 3,500 | 3,500 | 3,500 | 3,500 |
Face Area (ft²) | 15.4 | 15.4 | 15.2 | 15.2 | 15.2 |
Rows Deep/Fins per Inch | 1/24 | 1/24 | 2/16 | 2/16 | 2/16 |
|
|
|
|
|
|
Compressor |
|
|
|
|
|
|
|
|
|
|
|
Quantity / Type | 1 / Scroll | 1 / Scroll | 1 / Scroll | 1 / Scroll | 1 / Scroll |
|
|
|
|
|
|
Stage | Single | Single | Single | Single | Single |
|
|
|
|
|
|
Compressor RLA/LRA | 19.9/109 | 19.9/109 | 26.4 / 134 | 26.4 / 134 | 26.4 / 134 |
|
|
|
|
|
|
Electrical Data |
|
|
|
|
|
Voltage/Phase/Frequency | |||||
Indoor Blower FLA/LRA | 5.8 | 5.8 | 7.6 | 7.6 | 7.6 |
Outdoor Fan RLA/LRA | 1.4/ 2.9 | 1.4/ 2.9 | 1.4/ 2.9 | 1.4/ 2.9 | 1.4/ 2.9 |
Total Unit Amps | 27.1 | 27.1 | 35.4 | 35.4 | 35.4 |
Min. Circuit Ampacity | 32.1 | 32.1 | 42 | 42 | 42 |
Max. Overcurrent Protection | 50 amps | 50 amps | 60 amps | 60 amps | 60 amps |
Entrance Size Power Supply | 1⅛” | 1⅛” | 1⅛” | 1⅛” | 1⅛” |
Entrance Size Control Voltage | ⅞” | ⅞” | ⅞” | ⅞” | ⅞” |
Operating Weight (lbs) | 523 | 528 | 533 | 538 | 543 |
Ship Weight (lbs) | 545 | 550 | 555 | 560 | 565 |
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² Must use
Note: Always check the S&R plate for electrical data on the unit being installed.
www.goodmanmfg.com | 5 |