This equipment is furnished with factory
Filter Installation (See Figure #2 on page 7)
All 4 stages of filters are shipped on a separate skid in the original factory packaging. Do not remove packaging or install filters until just prior to commissioning the unit.
Care must be taken to ensure filters are installed in the proper sequence and proper direction of airflow for filter stages 1, 2 & 3 (stage 4 carbon panels are not subject to airflow direction).
Open the access doors. Remove the filter compression plates at stages 1, 2, 3 & 4. Install filters and replace all 4 filter compression plates. Compression plates must be in place to ensure proper filter sealing integrity. Close and latch access doors.
NOTE
Access doors are on lift off hinges and can be easily removed for more convenient filter servicing.
Filter Stage | Dimensions (inches) | |
Description | ||
| ||
|
| |
| 24 x 24 x 4 thick | |
MERV 8 | ||
(Stage 1) | ||
Pleated metal frame filter | ||
| ||
|
| |
Bag Filter | 24 x 24 x 22 deep | |
MERV 14 | ||
(Stage 2) | ||
Bag filter | ||
| ||
|
| |
Rigid Filter | 24 x 24 x 12 thick | |
MERV 16 | ||
(Stage 3) | ||
95% DOP | ||
| ||
|
| |
Carbon Panel | 24 x 24 x 1 thick | |
(Stage 4) | Bonded carbon panel | |
|
|
NOTE
Only UL 900, Class 1 filters are approved for use in this equipment. Substitutions will void the manufacturer’s warranty and the listing to UL
710.Please refer to the Maintenance section for information on ordering replacement filters.
Operation
NOTE
Prior to starting the fan, remove fan tie down straps. These are used only to prevent shipping damage. After removing the tie down straps, the fan should float freely on the spring isolators. Confirm that the installation is completed as shown in the Installation section.
Start-Up
Turn the unit on momentarily and then turn off. Remove fan drive access cover and verify proper fan wheel rotation. If rotation is backwards, reverse the fan motor electrical input leads. After verifying proper fan wheel rotation, the unit is ready for operation.
Filter Status Indicator
As filter stages 1, 2 and 3 load with smoke and grease particles, resistance to airflow increases and the exhaust air volume decreases. Pressure switches continuously read the resistance across each filter stage. Each pressure switch is factory preset to transmit an alarm signal when that stage of filter has reached its terminal resistance and needs replacing with new filters. This terminal resistance setting is based on the filter manufacturers rating. The alarm signal lights an LED located on the face panel of the remote Filter Status Indicator Enclosure.
IMPORTANT
Replace filters immediately after the Filter Status Indicator light comes on. Failure to do so may cause a reduced exhaust air volume allowing smoke to escape into the kitchen, or may cause filters to rupture, or both. The terminal resistance for each stage of filters is factory set at the values shown below. Altering these settings without first contacting Greenheck Fan Corp. will void the manufacturers warranty and void the UL 710 listing.
Filter Stage | Resistance Setting |
1 | 1.2 in. wg. |
|
|
2 | 1.0 in. wg. |
|
|
3 | 1.7 in. wg. |
|
|
Grease Grabber Triple Play Kitchen Exhaust Pollution Control System 5