DFD-150X series
Dynamic Rated FIRE DAMPERS with Sleeve
11⁄2 Hour Fire Resistance Rating
APPLICATION
Model
555 classifies dynamic rated fire dampers for use in HVAC systems that are operational in the event of fire .
RATINGS
UL555 Fire Resistance Rating Fire Rating: 1 1/2 hours
Dynamic closure rating
Maximum Velocity: 4000 fpm (20.3 m/s) up to 24 in. x 24 in. (610mm x 610mm) 2000 fpm (10.2 m/s) above
24 in. x 24 in. (610mm x 610mm) Maximum Pressure: 4 in. wg (1 kPa)
Model
National Fire Protection Association
(NFPA Standards 80, 90A & 101)
BOCA National Building Codes
ICBO Uniform Building Codes (UBC Standard
SBCCI Standard Building Codes
New York City (MEA listing
California State Fire Marshall (Listing #3225-981:102 for use in walls)
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555 (Listing #R13317)
CONSTRUCTION
Damper is galvanized steel (in gauges required by UL listing
STANDARD FEATURES
•Stainless steel closure springs
•Fusible links (165ºF (74ºC) standard, 212ºF (100ºC) and 286ºF (141ºC) available.
•Horizontal or vertical mount available
OPTIONAL FEATURES
•Security bars
•One piece retaining angles (POC)
•Transitions (B, C, CO, CR, & R)
•Steel stud connection
•Sealed transitions and sleeves
SleeveDamper
P *
H *
Fusible Link (replaceable)
K |
|
|
Damper | C Damper Fram e |
|
Location | L | W * |
|
Overall Sleeve Length
10 in. (305mm) =
12 in. (305mm) =
14 in. (356mm) =
16 in. (406mm) =
VERTICAL MOUNT
*These dimensions are furnished approximately 1⁄4 in. (6mm) undersize.
K
CL Damper
Frame
HORIZONTAL MOUNT