VARIABLE MAKE-UP AIR OPTIONS
Variable Volume
The variable volume option is recommended when a building’s exhaust volume will vary. The
The variable volume option saves energy by reducing both fan power and gas consumption whenever make- up air requirements are less than the maximum.
Airflow Control Strategies
Greenheck offers four methods of controlling the
•Variable Frequency Drive controlled by building pressure.
•Variable Frequency Drive controlled manually with a remote potentiometer.
•Variable frequency drive controlled by a
•2 speed motor controlled manually with a remote switch.
Burner By-Pass Damper
The Variable Volume option includes a patented burner
Outside Air
Supply Air
Recirculation
The recirculation option is recommended when the ventilation equipment provides the primary source of heating for the space.
Up to 80% of the air from the space can be recirculated and filtered and then combined with a minimum of 20% outdoor air for a continuous source of fresh air. Only outdoor air is used for combustion to eliminate the possibility of contaminants from the recirculated air crossing over the burner.
Airflow Control Strategies
Greenheck offers four methods of controlling the ratio of recirculated air to outdoor air via motorized dampers.
• Modulating actuator controlled by building pressure.
•Modulating actuator controlled manually with a remote potentiometer.
•Modulating actuator controlled by a
•Two position actuator controlled manually with a remote switch/time clock.
20%
Outside Air
Recirculated Air | Supply Air |
|
Temperature Control
There are three temperature control options for heat: 1) Discharge Control, 2) Space Control, and 3) DDC Interface Control. Cooling controls are by others.
Discharge Control
A factory installed modulating system controls the gas valve to provide the desired temperature based on a sensor at the fan discharge. A room override option is available to boost the discharge temperature when the space is too cool.
Room Control
Specify this option when the DGX has the primary responsibility for controlling the room temperature. A manually adjusted room thermostat provides feedback to the unit controls, which vary the discharge temperature in order to maintain desired room set point.
DDC Interface Control
Allows for an external signal
4