Performance

Supply and Exhaust - Belt Drive

Model ERV-521

Model ERV-522

Model ERV-581

Model ERV-582

ERV-521S (Standard Airflow)

CFM

OV

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.125

0.25

0.375

0.50

0.75

1.00

1.25

1.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2,200

2,183

 

FRPM

830

881

933

981

1072

1155

1238

1315

 

BHP

0.72

0.80

0.87

0.95

1.09

1.25

1.41

1.57

 

 

 

2,700

2,679

 

FRPM

998

1040

1081

1124

1203

1278

1350

1416

 

 

 

 

 

 

 

 

 

 

 

BHP

1.29

1.38

1.47

1.57

1.75

1.93

2.12

2.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3,200

3,175

 

FRPM

1168

1203

1240

1274

1345

1412

1477

 

 

 

 

 

 

 

 

 

 

 

 

BHP

2.11

2.21

2.32

2.43

2.65

2.86

3.08

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERV-521H (High Airflow)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

OV

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.125

0.25

0.375

0.50

0.75

1.00

1.25

1.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3,100

3,076

 

FRPM

980

1017

1054

1089

1159

1226

1290

1355

 

 

 

 

 

 

 

 

 

 

 

BHP

1.57

1.65

1.73

1.82

1.99

2.18

2.36

2.54

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3,700

3,671

 

FRPM

1156

1187

1219

1249

1309

1367

1425

1480

 

 

 

 

 

 

 

 

 

 

 

BHP

2.62

2.72

2.83

2.92

3.12

3.33

3.55

3.77

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4,300

4,267

 

FRPM

1334

1361

1388

1415

1467

1519

1569

 

 

 

 

 

 

 

 

 

 

 

 

BHP

4.08

4.20

4.31

4.43

4.65

4.89

5.13

 

 

 

 

 

ERV-522S (Standard Airflow)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

OV

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.125

0.25

0.375

0.50

0.75

1.00

1.25

1.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5,000

2,416

 

FRPM

754

794

831

869

943

1011

1072

1134

 

 

 

 

 

 

 

 

 

 

 

BHP

2.20

2.39

2.57

2.76

3.15

3.54

3.89

4.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5,750

2,779

 

FRPM

855

892

924

957

1022

1087

1146

1201

 

BHP

3.28

3.49

3.70

3.92

4.33

4.81

5.26

5.67

 

 

 

6,500

3,141

 

FRPM

956

991

1021

1049

1108

1164

1222

1276

 

 

 

 

 

 

 

 

 

 

 

BHP

4.67

4.90

5.15

5.39

5.88

6.33

6.89

7.41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERV-522H (High Airflow)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

OV

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.125

0.25

0.375

0.50

0.75

1.00

1.25

1.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6,000

2,067

 

FRPM

535

581

619

660

731

797

857

913

 

BHP

1.57

1.79

1.96

2.16

2.55

2.94

3.33

3.72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7,500

2,584

 

FRPM

646

686

722

753

818

877

930

983

 

 

 

 

 

 

 

 

 

 

 

BHP

2.90

3.20

3.46

3.68

4.17

4.66

5.12

5.62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9,000

3,100

 

FRPM

763

794

827

857

910

964

1016

1063

 

 

 

 

 

 

 

 

 

 

 

BHP

4.90

5.20

5.57

5.89

6.42

7.01

7.60

8.18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERV-581H (High Airflow)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

OV

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.125

0.25

0.375

0.50

0.75

1.00

1.25

1.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4,300

2,064

 

FRPM

637

687

733

772

850

923

988

1055

 

 

 

 

 

 

 

 

 

 

 

BHP

1.20

1.35

1.49

1.61

1.88

2.16

2.42

2.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5,050

2,424

 

FRPM

731

774

817

855

922

989

1053

1111

 

 

 

 

 

 

 

 

 

 

 

BHP

1.89

2.05

2.23

2.39

2.68

3.00

3.33

3.65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5,800

2,784

 

FRPM

826

866

903

939

1004

1061

1120

1177

 

BHP

2.79

2.99

3.18

3.38

3.74

4.07

4.44

4.83

 

 

 

ERV-582H (High Airflow)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

OV

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.125

0.25

0.375

0.50

0.75

1.00

1.25

1.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9,000

2,254

 

FRPM

595

629

661

692

746

797

843

888

 

 

 

 

 

 

 

 

 

 

 

BHP

3.61

3.95

4.26

4.54

5.25

5.89

6.48

7.09

 

 

 

10,500

2,630

 

FRPM

685

713

741

769

820

867

911

952

 

BHP

5.60

5.99

6.38

6.74

7.44

8.27

9.03

9.74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12,000

3,005

 

FRPM

776

800

825

849

897

941

982

 

 

 

 

 

 

 

 

 

 

 

 

BHP

8.24

8.66

9.12

9.56

10.36

11.19

12.13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gross supply air performance ratings (airflow, pressure, and power) are at port 2 with port 1, port 3 and port 4 at 0.0 in. wg. Gross exhaust air performance ratings (airflow, pressure, and power) are to port 3 with port 1, port 2 and port 4 at 0.0 in. wg. Power rating (Bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.

13

Page 13
Image 13
Greenheck Fan manual Supply and Exhaust Belt Drive, Model ERV-521 Model ERV-522 Model ERV-581 Model ERV-582

ERV specifications

Greenheck Fan's Energy Recovery Ventilator (ERV) represents a significant advancement in the field of indoor air quality and energy efficiency. These systems are designed to provide balanced ventilation while recovering energy from exhaust air, making them an ideal choice for commercial and industrial applications.

One of the main features of the Greenheck ERV is its energy recovery core, which effectively transfers heat and moisture between the incoming and outgoing airstreams. This technology allows for a significant reduction in heating and cooling costs by pre-conditioning the incoming air, resulting in less strain on HVAC systems. The core is engineered for high efficiency, delivering seasonal energy savings and contributing to LEED certification for green buildings.

Another notable characteristic of the Greenheck ERV is its versatility. The units come in various sizes and configurations to meet different building specifications and ventilation requirements. They are suitable for a wide range of applications, from schools and offices to hospitals and industrial spaces. Users can customize the ERV to suit specific needs, including options for enhanced filtration, integrated controls, and multiple airflow configurations.

The construction quality of Greenheck ERVs is also commendable. They feature robust materials that ensure long-lasting performance and durability, even in demanding environments. The units are designed to withstand harsh outdoor conditions, making them reliable for year-round operation. Furthermore, the noise levels are minimized thanks to their well-engineered design, providing a comfortable indoor environment free of distracting sounds.

Greenheck has incorporated advanced controls and monitoring technologies into its ERV systems. This feature allows users to track performance, optimize energy use, and maintain indoor air quality. The controls can be integrated with building management systems for seamless operation. Moreover, the units are designed for ease of maintenance, with accessible components that simplify servicing and repairs.

In summary, Greenheck Fan's Energy Recovery Ventilator combines energy efficiency, versatility, and advanced technology to deliver exceptional indoor air quality solutions. Its energy-recovery capabilities, adaptability to various applications, durable construction, and advanced controls position it as a leading choice in the market for energy recovery and ventilation solutions.