Part #462102
INSTALLATION INSTRUCTION SUPPLEMENT
®
Refer to:
‘Installation Instructions for FD, DFD, SSFD, & KFD Models’ (Part #452763)
or
‘Installation Instructions for
or
‘Installation Instructions for FD & DFD 150X Series Curtain Fire Dampers’ (Part #453946) for additional details.
Notes
1. | Gypsum panels must be screwed 12 in. (305mm) on center |
| maximum to all stud and runner flanges surrounding |
| opening. (See Figure 1 for Opening Preparation Details). |
2. | Fire damper and sleeve assemblies 80 in. W x 50 in. H |
| (2032mm x 1270mm), 50 in. W x 80 in. H |
| (1270mm x 2032mm), or 40 in. W x 100 in. H |
| (1016mm x 2540mm) and smaller only require retaining |
| angles on one side of the partition. (See Figure 2 and |
| Figure 3). Retaining angles must be attached to the |
Wood Stud Framing for Fire Dampers in Drywall Partitions Utilizing One Retaining Angle
FD & DFD Series
11/2 Hour Curtain Fire Dampers and
FSD & SSFSD Series
11/2 Hour Combination Fire Smoke Dampers Vertical Mount
“UL CLASSIFIED
(see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standards UL 555 & 555S Classifications Filed at UL under Listing #R13317
sleeve and the partition. Larger damper assemblies require |
retaining angles on both sides of the partition. Retaining |
angles must be attached to the sleeve. |
• Retaining angles must be a minimum of 16 gauge (1.5mm) |
steel and have a minimum of 11/2 in. x 21/2 in. legs |
(38mm x 63mm). |
• Retaining angles must be attached to the sleeve using |
one of the methods shown below: |
• tack or spot welds |
• #10 sheet metal screws and bolts |
• Retaining angles must be attached to the partition using |
drywall screws of a length such that the screw engages |
the stud by a minimum of 1 3/4 in. (44mm) |
• A minimum of two connections per side, top, and bottom, |
12 in. (305mm) O.C. maximum for openings of |
48 in. W x 36 in. H (1219mm x 914mm) and less, and |
6 in. (152mm) O.C. for openings 80 in. W x 50 in. H |
(2032mm x 1270mm), 50 in. W x 80 in. H, |
12 in.
24 in. o.c. Maximum
24 in. o.c. | 24 in. o.c. | Ceiling Runner | |
Maximum | Maximum | ||
| |||
(metal studs) | (metal studs) |
| |
|
| 2 in. | |
| 2 Panhead |
| |
| Screws | 2 in. | |
|
| ||
16 in. o.c. | 16 in. o.c. |
| |
Maximum | Maximum |
| |
(wood studs) | (wood studs) |
|
(1270mm x 2032mm) and 40 in. W x 100 in. H |
(1016mm x 2540mm)or less. |
• Retaining angles must overlap the partition a minimum of |
1 in. (25mm) |
Floor Runner
Figure #1: Opening Preparation Detail (double vertical studs are not required for openings 36 in. x 36 in. [914mm x 914mm] or smaller)
Damper
Sleeve
2 1/2 in. Min. |
Stud or Runner |
1/2 in. UL Classified |
Gypsum Wallboard (see |
UL Rated Wall Design |
for Additional Details) |
Angle Fastener (see Note 2)
11⁄2 in. x 21⁄2 in.
16 ga. angle
Figure #2: 1 Hour Wall Rating
Damper |
Sleeve |
2 1/2 in. Min. |
Stud or Runner |
1/2 in. UL Classified |
Gypsum Wallboard (see |
UL Rated Wall Design |
for Additional Details) |
Angle Fastener (see Note 2)
11⁄2 in. x 21⁄2 in. 16 ga. angle
Figure #3: 2 Hour Wall Rating
Copyright © 2008 Greenheck Fan Corporation
462102 Wood Stud Supplement
Rev. 4 March 2008