| Model | |||
APPLICATION | Combination Fire Smoke Dampers | ||||||||
|
|
|
| Steel Airfoil Blades | |||||
Model |
|
|
| ||||||
|
|
| UL 555S Leakage Class II | ||||||
damper with class II leakage. High strength airfoil blades ensure the |
|
|
| ||||||
| UL555 11⁄2 Hour Fire Resistance Rating | ||||||||
lowest resistance to airflow in HVAC systems with velocities to 3000 |
| ||||||||
fpm (15.2 m/s) and pressures to 4 in. wg (1 kPa) Model |
|
|
|
|
|
| |||
be installed vertically (with blades running horizontal) or horizontally | Model | ||||||||
and is rated for airflow and leakage in either direction. | dampers, smoke dampers and combination fire | ||||||||
Ratings |
| smoke dampers established by: | |||||||
| National Fire Protection Association | ||||||||
UL 555 Fire Resistance Rating: |
| ||||||||
| NFPA Standards 80, 90A, 92A, 92B, 101 & 105 | ||||||||
Fire Rating: | 1½ hours | ||||||||
IBC International Building Codes | |||||||||
Dynamic Closure Rating: Actual ratings are size dependent | |||||||||
Max. Velocity: | up to 3000 fpm (15.2 m/s) | ICBO Uniform Building Codes | |||||||
Max. Pressure: | 4 in. wg (1 kPa) | CSFM California State Fire Marshal | |||||||
UL555S Leakage Rating: |
| Fire Damper Listing | |||||||
| Leakage (Smoke) Damper Listing | ||||||||
Leakage Class: | II | ||||||||
Operational Rating: | Actual ratings are size dependent | New York City (MEA listing | |||||||
Max. Velocity: | up to 3000 fpm (15.2m/s) |
|
|
|
|
|
| ||
Max. Pressure: | 4 in. wg (1 kPa) |
|
|
|
|
|
| ||
Maximum Temperature: 350°F (177°C)- depending upon the | “UL CLASSIFIED (see complete marking on prod- | ||||||||
|
| actuator | uct)” |
|
|
|
|
| |
Standard Construction | “UL CLASSIFIED to Canadian safety standards | ||||||||
(see complete marking on product)” | |||||||||
Frame: | 5 in. x 1 in. (127mm x 25 mm) | Standard 555 & 555S (Listing #R13317) | |||||||
|
| galvanized steel hat channel with |
|
|
|
|
|
| |
|
| reinforced corners. A low profile |
|
| Greenheck Fan Corporation certifies that the | ||||
|
| head and sill are used on sizes less |
|
| |||||
|
| than 17 in. (432mm) |
|
| model | ||||
|
|
|
| bear the AMCA Seal. The ratings shown are | |||||
Blades: | Double skin airfoil shape of |
|
| ||||||
|
| based on tests and procedures performed | |||||||
|
| galvanized steel with full length |
|
| in accordance with AMCA Publication 511 | ||||
|
| structural reinforcement. 14 ga. |
|
| and comply with the requirements of the | ||||
|
| (2 mm) equivalent thickness. |
|
| AMCA Certified Ratings Programs. The | ||||
|
| R |
| AMCA Certified Ratings Seal applies to air | |||||
Seals: | Extruded silicone rubber blade seals. |
|
| performance ratings only. | |||||
|
| Flexible stainless steel jamb seals. |
|
|
|
|
|
| |
Linkage: | Concealed in jamb. |
|
|
|
|
|
| ||
Closure Device: | RRL 165°F (74°C) |
|
|
|
|
|
| ||
Axles: | 1⁄2 in. (13mm) dia. plated steel. |
|
|
|
|
|
| ||
Bearings: | Bronze sleeve type. |
|
|
|
|
|
| ||
Size Limitations: | 8 in. W x 6 in. H |
|
|
|
|
|
| ||
Minimum Size: |
|
|
|
|
|
| |||
Maximum Size: | (203 mm W x 152mm H) |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |||
Single Section: | 32 in. W x 50 in. H |
|
|
|
|
|
| ||
|
| (813mm W x 1270mm H) |
|
|
|
|
|
| |
Multiple Section: | 96 in. W x 50 in. H |
|
|
|
|
|
| ||
|
| (2435mm W x 1270mm H) |
|
|
|
|
|
| |
Vertical Only: | 128 in. W x 100 in. H |
|
|
|
|
|
| ||
|
| (3251mm W x 2540mm H) |
|
|
|
|
|
| |
Optional Features: | LH |
|
|
| H* | ||||
|
|
|
| ||||||
• RRL/OCI (Open closed indication switches) |
|
|
|
| |||||
• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL’s |
|
|
|
|
|
| |||
available |
|
|
|
|
|
|
| ||
• TOR (remote override closure allows damper to perform smoke |
|
|
|
|
|
| |||
management functions during a fire emergency.) |
|
|
|
|
|
| |||
|
| W* |
|
|
| ||||
• Electric or pneumatic actuators to accomplish smoke |
|
|
|
|
| ||||
management and system functions. |
|
|
|
|
|
| |||
|
|
|
| RH | |||||
• POC retaining angles |
|
|
|
|
| ||||
• Smoke detectors |
| *W&H dimensions furnished approximately 1/4 in. ( 6 mm) undersize. | |||||||
• Momentary Switch |
| ||||||||
• Transitions (R, C, O) |
| (Add sleeve thickness for overall sleeved damper dimension) | |||||||
| Right hand drive is shown. Left hand drive is available upon request. | ||||||||
• PRV (pneumatic relief valve) |
| ||||||||
|
|
|
|
|
|
|
• Security Bars |
|
• Sealed transitions and sleeves | Installation instructions available at www.greenheck.com |
|