Greenheck Fan H-CUBE, H-GB Typical Installation, Fan to Curb Mounting, Concrete Deck Anchoring

Models: H-CUE H-G H-GB H-CUBE

1 8
Download 8 pages 11.71 Kb
Page 4
Image 4

Typical Installation

®

Fan to Curb Mounting

H-G

H-GB

Fasteners

Total

Size

Size

Per Side

Fasteners

 

 

 

 

060 - 141

098 - 161

3

12

 

 

 

 

150 - 180

180 - 300

5

20

 

 

 

 

Fan to curb tie down is not required to meet 150 MPH wind loads for size 240 and smaller.

H-CUE

H-CUBE

Fasteners

Total

Size

Size

Per Side

Fasteners

 

 

 

 

060 - 161

098 - 161

3

12

 

 

 

 

180 - 200

180 - 240

5

20

 

 

 

 

-

300

9

36

 

 

 

 

Model H-G

or

H-GB

Tie Down is optional on sizes 060 - 240

Fastener

H-GPF or SD Curb

Model H-CUE

or

H-CUBE

Fastener

Fasteners on each side of the fan are to be installed with one fastener 4 inches (102 mm) from each edge and one fastener centered. The remaining fasteners are to be equally spaced.

Typical Installation

Concrete Deck Anchoring

 

 

 

 

 

 

 

 

 

 

 

Outside of Roof Curb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1 inch (25 mm) less than

 

 

 

 

 

 

 

 

 

 

 

Fan Curb Cap)

1¼ inch (32 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H-GPF Curb Height

 

 

1 inch (25 mm) Insulation

 

 

 

 

 

 

 

8 to 18 inches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1¼ inch

 

(203 to 457 mm)

 

 

 

 

 

 

 

 

 

 

(Optional 24 inch

 

 

 

 

 

 

 

 

 

(32 mm)

 

 

 

 

 

 

 

 

 

 

 

(610 mm) SD Curb)

 

 

 

Roof Opening

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Concrete

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Strength of 2000 PSI

 

 

 

Corner Detail

 

Minimum 1¾ inch

 

 

 

 

 

 

 

 

 

(44 mm) edge distance

 

 

 

 

 

 

 

 

 

 

 

 

 

5 inch (127 mm) Mounting Flange

 

 

 

 

 

 

 

 

 

 

 

Outside Flange

Use 3/8 inch (10 mm) expansion anchor or equal into concrete.

Fasteners one on each corner as detailed.

Each side at center of unit. Maximum fastener spacing of 8 inches (203 mm), add additional fasteners to satisfy.

2½ inch (64 mm)

Embedment Recommended.

Minimum 15/8 inch (41 mm).

Center fasteners on flange

H-G

H-GB

H-CUE

H-CUBE

Fan Curb Cap

Roof Opening

Fasteners

Outside Flange

Size

Size

Size

Size

Per Side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060 - 075

 

-

060 - 075

 

-

17 x 17 (432 x 432)

10½ x 10½ (267 x 267)

5

26 x 26 (660 x 660)

 

 

 

 

 

 

 

 

 

 

 

 

080

- 095

 

-

 

-

 

-

17 x 17 (432 x 432)

12½ x 12½ (318 x 318)

5

26 x 26 (660 x 660)

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

-

080

- 095

 

-

19 x 19 (483 x 483)

12½ x 12½ (318 x 318)

5

28 x 28 (711 x 711)

 

 

 

 

 

 

 

 

 

101

- 121

071 - 131

098 - 131

098 - 131

19 x 19 (483 x 483)

14½ x 14½ (368 x 368)

5

28 x 28 (711 x 711)

 

 

 

 

 

 

 

 

 

 

 

 

131

- 141

141

- 161

141

- 161

141

- 161

22 x 22 (559 x 559)

18½ x 18½ (470 x 470)

5

31 x 31 (787 x 787)

 

 

 

 

 

 

 

 

 

 

 

 

 

150

 

-

 

-

 

-

26 x 26

(660 x 660)

18½ x 18½ (470 x 470)

5

35 x 35

(889 x 889)

 

 

 

 

 

 

 

 

 

 

 

160

- 180

180 - 200

180 - 200

180 - 200

30 x 30

(762 x 762)

20½ x 20½ (521 x 521)

7

39 x 39

(991 x 991)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

220

- 240

 

-

220

- 240

34 x 34

(864 x 864)

26½ x 26½ (673 x 673)

7

43 x 43

(1092 x 1092)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

260

- 300

 

-

300

40 x 40

(1016 x 1016)

32½ x 32½ (826 x 826)

7

49 x 49

(1245 x 1245)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4All dimensions in inches (millimeters).