Greenheck Fan none installation instructions Part number, SMD, SESMD, & SSSMD Series

Models: none

1 3
Download 3 pages 11.51 Kb
Page 1
Image 1
Part number 465915

 

 

 

 

 

 

 

Part number 465915

 

 

 

 

 

 

 

Installation Instruction Supplement for

 

 

 

 

 

 

 

SMD, SESMD, & SSSMD Series

 

Refer to:

 

‘Installation Instructions for SMD, SESMD, and

 

Smoke Dampers and

SSSMD Series Leakage Rated Smoke Dampers’

 

FSD, FSD-3XXV, SEFSD, & SSFSD Series

(Part #461338)

 

 

or

Combination Fire Smoke Dampers

‘Installation Instructions for CFSD, FSD, DFD,

 

SEFSD, SSFSD Series Combination Fire Smoke

 

 

 

Dampers’ and (Part#461336) and FSD-3XXV series

with Factory Mounted No Flow Duct Smoke Detectors

 

 

(Part #461666) for additional details

 

 

 

 

 

 

 

 

 

NOTES

1.Minimum air velocity for smoke detector operation is 0 fpm. Maximum is 3000 fpm.

2.Model 2151 low profile smoke detector is mounted to a standard electrical box within the duct. The twist-in/ twist-out head allows easy removal from the base for quick cleaning and maintenance.

3.Smoke detector specifications are:

Operating temperature rating: 32°F to 120°F (0°C to 49°C) Operating humidity range: 10% to 93% RH

Operation voltage: 120 VAC

4.Refer to System Sensor, 2151, Installation and Maintenance Instructions for further installation details.

5.Refer to System Sensor, 2151, Installation and Maintenance Instructions for maintenance and field tests.

6.System Sensor 3825 Ohio Avenue

St. Charles, IL 60174

Phone: 1-800-736-7672

Fax: 1-630-377-6495

Website: www.systemsensor.com

UL CLASSIFIED (see complete marking on product)

UL CLASSIFIED to Canadian safety standards (see complete marking on product)

Standard 555 (Listing #R13317)

Standard 555S (Listing # R13447)

#10 TEK SCREW

4 X 4 X 2 1/8 HANDI BOX

SMOKE DETECTOR ASSEMBLY

Page 1
Image 1
Greenheck Fan none installation instructions Part number, SMD, SESMD, & SSSMD Series, FSD, FSD-3XXV, SEFSD, & SSFSD Series