IMPORTANT

Adjust (tighten) belt tension after the first 24-48 hours of operation.

Maintenance: NYD/NYB

A proper maintenance program will help these units deliver years of dependable service. Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations and who are experienced with this type of equipment.

Motor maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be limited to exterior surfaces only. Removing dust buildup on motor housing ensures proper motor cooling.

Greasing of motors is only intended when fittings are provided. Many fractional horsepower motors are permanently lubricated and should not be lubricated after installation. Motors supplied with grease fittings should be greased in accordance with manufacturers’ recommendations. Where motor temperatures do not exceed 104ºF (40ºC), the grease should be replaced after 2,000 hours of running time as a general rule.

Direct drive units require little maintenance except for cleaning wheel, alignment and oiling according to motor label instructions.

The unit should be made non-functional when cleaning the wheel or housing (fuses removed, disconnect locked off, etc.).

Wheels require very little attention when moving clean air. Occasionally, oil and dust may accumulate causing imbalance. When this occurs the wheel and housing should be cleaned to ensure smooth and safe operation.

All fasteners should be checked for tightness each time maintenance checks are performed prior to restarting unit.

A proper maintenance program will help these units deliver years of dependable service.

Belt/Bearing Maintenance NYB Unit

1.Belts tend to stretch after a period of time. They should be checked periodically for wear and tightness. When replacing belts, use the same type as supplied with the unit.

2.Matched belts should always be used on units with multi-groove pulleys.

3.For belt replacement, loosen the tensioning device enough to allow removal of the belt by hand. Do not force the belts on or off. This may cause cords to break, leading to premature failure.

4.Once installed, adjust belts as shown in “PreStarting Checks.”

5.Shaft bearings can be classified in two groups: relubricating and non-relubricating. All bearings are factory lubricated and require no further lubrication under normal use (between -20ºF and 180ºF in a relatively clean environment).

6.Units installed in hot, humid or dirty locations should be equipped with special bearings. These bearings will require frequent lubrication.

7.On NYB belt driven fans, the standard cast pillow block bearings are factory lubricated and are provided with external grease fittings. Annual lubrication is recommended, or more frequently if needed, see Table 2. Do not over- grease. Use only one or two shots of lubricant with a hand gun. Maximum hand gun rating is 40 psi. Rotate bearings during lubrication where good safety practice permits. Caution should be employed to prevent over packing or contamination.

7.Grease fittings should be wiped clean. The unit should be in operation while lubricating. Extreme care should be used around moving parts.

8.Grease should be pumped in very slowly until a slight bead forms around the seal. A high grade lithium base grease should be used.

9.To ensure tightness, check pulley setscrews. Proper keys must be in keyways.

10.Fan RPM should not be readjusted. Only use pulleys of identical size and type when replacing pulleys.

11.During the first few months of operation check bearing setscrews periodically to ensure tightness.

12.If unit is to be left idle for an extended period, remove belts and store in a cool, dry place to avoid premature belt failure.

WARNING

Always disconnect, lock and tag power source before servicing. Failure to disconnect power source can result in fire, shock or serious injury.

CAUTION

Uneven cleaning of the wheel will produce an out of balance condition that will cause vibration in the fan.

WARNING

This unit should be made non-functional when cleaning the wheel or housing (fuses removed, disconnect locked off).

Models NYD & NYB • Tamper-Resistant Centrifugal Roof Exhaust Fans

®

5

Page 5
Image 5
Greenheck Fan manual Maintenance NYD/NYB, Belt/Bearing Maintenance NYB Unit

NYD, NYB specifications

Greenheck Fan has long been known as a leader in the HVAC industry, with a commitment to providing innovative solutions for various ventilation needs. Among their impressive lineup, the NYB and NYD series stand out, showcasing advanced engineering, energy efficiency, and robust performance.

The Greenheck NYB and NYD fans are designed specifically for commercial and industrial applications, focusing on building ventilation demands. The NYB series features belt-driven centrifugal fans, while the NYD series brings direct-drive technology to the table. This versatility allows these fans to accommodate a wide range of air handling applications, from exhaust to supply air scenarios.

One of the main features of the NYB series is its ability to handle high volumes of air at modest static pressures. This performance characteristic is ideal for environments such as warehouses, factories, and large commercial spaces where air turnover is crucial. The NYD series, on the other hand, excels in applications requiring quieter operation and reduced maintenance, thanks to its direct-drive design, which eliminates the need for belts and pulleys.

Both the NYB and NYD fans come equipped with several advanced technologies designed to enhance their efficiency and reliability. For instance, they often incorporate energy-efficient motors that comply with or exceed regulations set by agencies like the Department of Energy (DOE). This focus on energy efficiency not only reduces operational costs but also supports sustainability in building operations.

Durability is a key characteristic of both series, with robust construction materials that ensure longevity even in demanding environments. The fans typically feature heavy-gauge steel housings and high-quality coatings that resist corrosion, thereby extending their service life.

Moreover, these fans can be customized with various accessories, including adjustable dampers, filters, and sound attenuators, enabling them to meet specific application requirements. The easy installation and maintenance features add to their appeal, allowing for seamless integration into existing systems.

In summary, the Greenheck Fan NYB and NYD series represent cutting-edge options for any commercial or industrial ventilation system. Their combination of energy efficiency, advanced technologies, durability, and customization makes them a go-to choice for professionals seeking reliable and effective air management solutions.