Application Data

Application Data

Damper Sideplate and Sleeve Dimensional Data

The drawings below illustrate the factory standard sideplate and sleeve mountings for the SMD-401. The standard "A" dimen- sions listed in the table provide adequate space for the mounting of actuators and controls.

If space constraints are a problem the "A" dimension can be varied between 5 38 in. (136mm) and 12 in. (305mm).

Sideplate

6 in.

5 in.

A 12 in.**

 

 

"A" Dimension

 

in. (mm)

Sleeve

 

Sideplate

 

 

 

 

 

 

Standard

 

Maximum

 

 

 

 

 

 

 

 

 

 

 

All Dampers*

7 3/16 (183)

 

12 (305)

 

6 3/16 (157)

 

 

 

 

 

 

When height is

11 3/16

 

12

 

10 3/16

11 in. (279) or

(284)

 

(305)

 

(259)

less with OCI

 

 

 

 

 

 

 

 

 

 

 

*With the exception of dampers 11 in. (279mm) high or less (12 in. (305mm)high or less if width is greater than 64 in. (1625mm)) with OCI option.

**On dampers 11 in. (279mm) high or less (12 in. (305mm)high or less if width is greater than 64 in. (1625mm)) with OCI option, sideplate is 16 in. (406mm)

Sleeve

Damper Sideplate and Sleeve Dimensional Data 11/2" max.

Manual background 3 3/4"Manual background

Varies

53/8"

 

Manual background A Manual backgroundManual background 5" Manual backgroundManual background

Sleeve Length

T*

Manual background S Manual background

B*Manual background

Space Envelopes Required for Actuators and Accessories

Externally mounted actuators always require space outside of the damper sideplate or sleeve. The “S” dimen- sion illustrates the clearance required for various available actuators.

On dampers less than 18 in. (457mm) high, actuators may also require clearances above and/or below the sideplate or sleeve. “B” and “T” dimensions are worst case clear- ance requirements for some dampers less than 18 in. (457mm) high. All damper sizes under 18 in. (457mm) high do not require these worst case clearances. If space avail- ability above or below the damper sleeve is limited, each damper size should be individually evaluated.

Actuator

 

B*

 

T*

S

Type/Model

 

 

 

 

 

 

With OCI

 

With OCI

 

 

 

 

 

 

 

120 Volt AC

 

 

 

 

 

 

 

ML4XXX Series Honeywell

5

1/4 in. (133mm)

 

3/4 in. (19mm)

6 in. (152mm)

 

 

 

 

 

MS4XXX Series Honeywell

6 in. (152mm)

 

3/8 in. (10mm)

6 in. (152mm)

 

 

 

 

 

MS4120 Series Honeywell

6 in. (152mm)

 

3/8 in. (10mm)

6 in. (152mm)

 

 

 

 

 

 

 

 

24 Volt AC

 

 

 

 

 

 

 

ML8XXX Series Honeywell

5

1/4 in. (133mm)

 

3/4 in. (19mm)

6 in. (152mm)

 

 

 

 

 

MS8XXX Series Honeywell

6 in. (152mm)

 

3/8 in. (10mm)

6 in. (152mm)

 

 

 

 

 

MS8120 Series Honeywell

6 in. (152mm)

 

3/8 in. (10mm)

6 in. (152mm)

 

 

 

 

 

 

 

Pneumatic (psi)

 

 

 

 

 

331-4551 Siemens

1 in. (25mm)

 

6 1/4 in. (159mm)

6 1/2 in. (165mm)

 

 

 

 

 

 

331-2976 Siemens

2

3/8 in. (60mm)

 

12 1/8 in. (308mm)

9 1/4 in. (235mm)

 

 

 

 

 

 

MK2-7121 Invensys

3

3/4 in. (95mm)

 

16 1/2 in. (419mm)

10 in. (254mm)

 

 

 

 

 

 

* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .