DELUXE INLINE FAN
Dimensional Data
Model |
| A | B | C | D | E | F | G | Wt. |
|
|
|
|
|
|
|
|
|
|
110, 150, | 200 | 137/8 | 111/2 | 715/16 | 6 | 11/4 | 101/4 | 31/4 | 101/4 |
Outlet connection width is 1 inch - Mounting bracket width is 1½ inch For complete dimensional information, see CAPS submittal drawings. All dimensions are in inches.
Performance Data
CSP B
D dia.
Inlet
F x G
C
E
BA
Model | RPM | AMPS | Watts |
|
| CFM/Static Pressure in inches of WG |
|
| |||||
|
|
|
|
|
|
|
|
| |||||
| 0.000 | 0.100 | 0.125 | 0.250 | 0.375 | 0.500 | 0.625 | 0.750 | |||||
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
4,6 |
|
|
| CFM | 103 | 100 | 99 | 98 | 97 | 96 | 93 | 86 | |
950 | 1.14 | 80 |
|
|
|
|
|
|
|
|
| ||
Sones | 2.0 | 2.0 | 2.1 | 2.3 | 2.6 | 2.7 | 3.1 | 3.3 | |||||
|
|
|
| ||||||||||
4,6 |
|
|
| CFM | 151 | 149 | 149 | 148 | 147 | 145 | 142 | 134 | |
1050 | 1.70 | 129 | |||||||||||
Sones | 2.5 | 2.7 | 2.7 | 2.9 | 3.1 | 3.4 | 3.6 | 3.9 | |||||
|
|
|
| ||||||||||
4,6 |
|
|
| CFM | 186 | 184 | 183 | 182 | 180 | 178 | 175 | 169 | |
1100 | 2.20 | 173 |
|
|
|
|
|
|
|
|
| ||
Sones | 3.4 | 3.6 | 3.7 | 4.0 | 4.1 | 4.1 | 4.3 | 4.5 | |||||
|
|
|
| ||||||||||
4 Units available with 50 Hz motors (See CAPS for performance) | 6 Available with 277 volt motor. |
|
|
|
Performance certified is for Model CSP inline for installation type D: Ducted inlet, Ducted outlet. Performance ratings include the effects of a backdraft damper. Speed (RPM) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) from the test inlet duct in a hemispherical free field calculated per AMCA Standard 301. Values are for installation type D: Ducted inlet fan sone levels. Ratings do not include the effects of duct end correction. Ratings are based on 10 ft. of insulated duct. The AMCA Certified Ratings Seal applies to air performance only.
Model
Typical Specifications
Ceiling mounted exhaust fans shall be of the centrifugal direct drive type. The fan housing shall be constructed of steel. The plastic duct collar shall be a tapered sleeve for ease of connection to 3 and 4 inch round ductwork and shall include a backdraft damper. The grille shall be constructed of
The wheels shall be constructed of high strength polymer. The access for wiring shall be external. The motor disconnect shall be internal and of the plug in type. All fans shall bear the AMCA Certified Ratings Seal for sound and air performance. Model
Models
Ceiling mounted exhaust fans shall be of the centrifugal direct drive type. The fan housing shall be constructed of steel. The steel duct collar shall be 4 inch in diameter on the B50, B70, and B80 and 6 inch in diameter on the B90, B150, and B200 to accept 4 inch and 6 inch round ductwork and shall include a backdraft damper. The designer grille shall be constructed of
The motor shall be mounted on vibration isolators. The fan wheel shall be of the forward curved centrifugal type, constructed of calcium carbonate filled polypropylene and dynamically balanced. All fans shall bear the AMCA Certified Ratings Seal for sound and air performance and shall be UL/cUL Listed. Ceiling or wall mount fans shall be Model
Models
Ceiling mounted exhaust fans shall be of the centrifugal direct drive type. The fan housing shall be constructed of heavy gauge galvanized steel. The housing interior shall be lined with 1/2 inch acoustical insulation. The outlet duct collar shall include an aluminum backdraft damper on all
The access for wiring shall be external. The motor disconnect shall be internal and of the plug in type. The motor shall be mounted on vibration isolators. The fan wheel(s) shall be of the forward curved centrifugal type and dynamically balanced. All fans shall bear the AMCA Certified Ratings Seal for sound and air performance and shall be UL/cUL Listed. Ceiling or wall mount fans shall be Model SP as manufactured by Greenheck Fan Corporation, Schofield, Wisconsin.
Models
Duct mounted exhaust, supply or return air fans shall be of the centrifugal direct drive type. The fan housing shall be constructed of steel. The steel duct collar shall be 6 inch in diameter to accept 6 inch round ductwork and shall include a backdraft damper. The access for wiring shall be external. The motor disconnect shall be internal and of the plug in type.
The motor shall mounted on vibration isolators. The fan Wheel shall be of the forward curved centrifugal type, constructed of calcium carbonate filled polypropylene and dynamically balanced. All fans shall bear the AMCA Certified Ratings Seal for air performance and shall be UL/cUL Listed. Ceiling or wall mount fans shall be Model
Models
Duct mounted exhaust, supply or return air fans shall be of the centrifugal direct drive type. The fan housing shall be constructed of heavy gauge galvanized steel. The housing interior shall be lined with 1/2 inch acoustical insulation. The outlet duct collar shall include an aluminum backdraft damper and shall be adaptable for horizontal or vertical discharge. The access for wiring shall be external. The motor disconnect shall be internal and of the plug in type.
The motor shall be mounted on vibration isolators. The fan wheel(s) shall be of the forward curved centrifugal type and dynamically balanced. All fans shall bear the AMCA Certified Ratings Seal for air performance and shall be UL/cUL Listed. Ceiling or wall mount fans shall be Model CSP as manufactured by Greenheck Fan Corporation, Schofield, Wisconsin.
19