Greenheck Fan SQ manual Side Discharge, Discharge Configuration

Models: SQ

1 44
Download 44 pages 41.38 Kb
Page 7
Image 7
Side Discharge

Side Discharge

The side discharge option provides several advantages including removal of a system effect problem, increasing performance, or even reducing installation labor. The most notable is reducing system effects. Notice the example in figure 1 showing the air being discharged into the corner. It will take several duct lengths before the airflow becomes smooth again after making the turn. This is not the case with a side discharge. See figure 2; when the air comes into the fan at the corner and leaves the fan at the corner, the airflow is smoother and provides a more predictable system. Remember the duct length prior to or following the installation location should be approximately two to three wheel diameters to achieve catalog performance.

Discharge Configuration

Make sure the fan discharge is oriented in the same direction as it was originally ordered. The performance will change with different discharge positions. Right side discharge will give you 108% of cataloged performance and left side will give you 109% of cataloged performance. Use figure 3 to locate the orientation to fit your application. Figures 4 and 5 explain the proper side discharge definitions. Refer to the CAPS program or consult factory for performance modifications.

Fan

Figure 2

Fan

Figure 1

+12%+8%

+9%

+12%

Figure 3 - Percentages based on cataloged performance.

Left Side

Discharge

Inlet

Figure 4

Left Side

Discharge

Inlet

Figure 5

Inline

Discharge Configuration Discharge

 

Height

Width

Right Side

 

Discharge

Inline

Manual background Discharge

 

Height

Width

Right Side

 

Discharge

SQ Side Discharge

Duct Openings

Unit Size

Width

Height

 

 

 

60-75

978 (251)

878 (225)

80-95

1278 (327)

1178 (302)

100

1378 (352)

1378 (352)

120

1578

(403)

1578

(403)

130

1778

(454)

1778

(454)

140

1978

(505)

1978

(505)

160

2278

(581)

2278

(581)

BSQ Side Discharge

Duct Openings

Unit Size

Width

Height

 

 

 

70-80-90

1178 (302)

1178 (302)

100

1378 (352)

1378 (352)

120

1578 (403)

1578 (403)

130-130HP

1778 (454)

1778 (454)

140-140HP

1978 (505)

1978 (505)

160-160HP

2278 (581)

2278 (581)

180-180HP

2378 (606)

2378 (606)

200-200HP

2778

(708)

2778

(708)

240-240HP

2878

(733)

3478

(886)

300-300HP

3178

(810)

4178 (1064)

360-360HP

3278

(835)

3778

(962)

4203478 (886) 4378 (1114)

All dimensions in inches (millimeters).

7

Page 7
Image 7
Greenheck Fan SQ manual Side Discharge, Discharge Configuration