Standby 25 kW
OPERATING DATA
|
|
| STANDBY 25 kW |
|
KW RATING |
|
| 25 LP / 24 NG |
|
|
|
|
|
|
ENGINE SIZE |
|
| 1.6 Liter 4 cyl. |
|
|
|
|
|
|
GENERATOR OUTPUT VOLTAGE/KW - 60Hz |
| KW | AMP | CB Size |
120/240V, |
| 25 LP/24 NG | 104.2 LP/100 NG | 125 |
120/208V, |
| 25 | 87 | 100 |
|
|
|
|
|
GENERATOR LOCKED ROTOR KVA |
|
|
|
|
AVAILABLE @ VOLTAGE DIP OF 35% |
|
|
|
|
Single phase |
|
| 34 |
|
|
|
| ||
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) | Natural Gas | Propane | ||
|
| (ft3/hr.) | (gal/hr.) | cu ft/hr |
Exercise cycle |
| 60 | 0.65 | 24 |
25% of rated load |
| 161 | 1.76 | 64 |
50% of rated load |
| 253 | 2.77 | 101 |
75% of rated load |
| 345 | 3.79 | 138 |
100% of rated load |
| 437 | 4.81 | 175 |
|
|
|
|
|
ENGINE COOLING |
|
|
|
|
Air flow (inlet air including alternator and combustion air) | ft3/min. |
| 1,528 |
|
System coolant capacity | US gal. |
| 2.0 |
|
Heat rejection to coolant | BTU/hr. |
| 110,000 |
|
Max. operating air temp. on radiator | °C (°F) |
| 60 (150) |
|
Max. ambient temperature | °C (°F) |
| 50 (140) |
|
|
|
|
|
|
COMBUSTION AIR REQUIREMENTS |
|
|
|
|
Flow at rated power 60 Hz | cfm |
| 90 |
|
|
|
|
|
|
SOUND EMISSIONS IN DBA |
|
|
|
|
db(A) @ 23 feet in exercise mode |
|
| 62 |
|
db(A) @ 23 feet at normal operating load |
|
| 74 |
|
|
|
|
|
|
EXHAUST |
|
|
|
|
Exhaust flow at rated output 60 Hz | cfm |
| 249 |
|
Exhaust temp. at muffler outlet | °F |
| 1015 |
|
|
|
|
|
|
ENGINE PARAMETERS |
|
|
|
|
Rated synchronous RPM | 60 Hz |
| 3600 |
|
HP at rated KW | 60 Hz |
| 45 |
|
|
|
|
| |
POWER ADJUSTMENT FOR AMBIENT CONDITIONS |
|
|
| |
Temperature Deration |
|
|
|
|
3% for every 10 °C above - °C |
| 25 |
| |
1.65% for every 10 °F above - °F |
| 77 |
| |
Altitude Deration |
|
|
|
|
1% for every 100 m above - m |
| 183 |
| |
3% for every 1000 ft. above - ft. |
| 600 |
| |
|
|
|
|
|
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with