Guardian Technologies 05649 manual Operating Data, 60 kW

Models: 05649

1 4
Download 4 pages 60.18 Kb
Page 3
Image 3
OPERATING DATA

60 kW

OPERATING DATA

KW RATING

 

 

60

 

 

 

 

 

 

ENGINE SIZE

 

 

2.4 Liter

 

 

 

 

 

 

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

 

KW

AMP

CB Size

120/240V, 1-phase, 1.0 pf

 

60

250

300

 

 

 

 

 

GENERATOR LOCKED ROTOR KVA

 

 

 

 

AVAILABLE @ VOLTAGE DIP OF 35%

 

 

 

 

Single phase or 208/240 3-phase

 

 

120

 

 

 

 

ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)

Natural Gas

Propane

 

 

(ft3/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

 

123

1.34

49.3

25% of rated load

 

267

2.7

101

50% of rated load

 

483

5.0

183

75% of rated load

 

672

7.0

255

100% of rated load

 

862

9.0

327

 

 

 

 

 

ENGINE COOLING

 

 

 

 

Air flow (inlet air including alternator and combustion air)

ft3/min.

 

3,280

 

System coolant capacity

US gal.

 

2.5

 

Heat rejection to coolant

BTU/hr.

 

270,000

 

Max. operating air temp. on radiator

°C (°F)

 

60 (150)

 

Max. ambient temperature

°C (°F)

 

50 (140)

 

 

 

 

 

 

COMBUSTION AIR REQUIREMENTS

 

 

 

 

Flow at rated power 60 Hz

cfm

 

180

 

 

 

 

 

 

SOUND EMISSIONS IN DBA

 

 

 

 

Exercising at 7 meters

 

 

65

 

Normal operation at 7 meters

 

 

72

 

 

 

 

 

 

EXHAUST

 

 

 

 

Exhaust flow at rated output 60 Hz

cfm

 

494

 

Exhaust temp. at muffler outlet

°F

 

1,050

 

 

 

 

 

 

ENGINE PARAMETERS

 

 

 

 

Rated synchronous RPM

60 Hz

 

3600

 

HP at rated KW

60 Hz

 

94

 

 

 

 

 

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

 

 

 

Temperature Deration

 

 

 

 

3% for every 10 °C above - °C

 

25

 

1.65% for every 10 °F above - °F

 

77

 

Altitude Deration

 

 

 

 

1% for every 100 m above - m

 

915

 

3% for every 1000 ft. above - ft.

 

3000

 

 

 

 

 

 

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.

Page 3
Image 3
Guardian Technologies 05649 manual Operating Data, 60 kW