Symptom

Possible Cause

Remedy

 

Power off or loose electrical connection

Make sure main switch is ON. Check and tighten all connections.

 

Incorrect thermostat setting

Set thermostat correctly

No cooling

Defective contactor

Check for 24V at contactor coil.

 

Open circuit breaker of blown fuses

Reset or replace

 

Defective transformer

Check wiring - Replace it.

 

Interconnecting low voltage wiring damage

Replace thermostat wiring

 

Dirty filters

Clean & replace

 

Indoor air blockage

Check supply registers and return grills for blockage.

 

Blocked outdoor coil

Clear away leaves and other debris

 

Improperly sized unit

Recalculate load

Insufficient Cooling

Improper airflow

Check - should be 400CFM/Ton

 

Incorrect refrigerant charge

Charge correctly per instruction.

 

Air, non-condensibles or moisture in system

Recover refrigerant, evacuate & recharge, add filter drier

 

Incorrect voltage

At compressor terminals, voltage must be within

 

 

10% of rating plate volts when unit is running.

Water on floor or in

 

 

furnace

Blocked condensate drain and "P" trap

Remove blockage

 

 

 

 

Run or start capacitor defective

Replace

 

Loose connection

Check and tighten all connections.

Condenser fan runs,

Compressor stuck, grounded or open

Wait for 2 hours for overload to reset.

compressor doesn't

motor winding, open internal overload

Replace compressor if still open.

 

Low voltage condition

At compressor terminals, voltage must be within 10% of rating

 

 

plate volts when unit is running.

 

Low voltage condition

Add start kit components

 

Incorrect voltage

At compressor terminals, voltage must be within 10% of rating

Compressor

 

plate volts when unit is running.

short-cycling

Defective overload protector

Replace - check for correct voltage

 

Refrigerant undercharge

Add refrigerant

Register sweat

Low evaporator airflow

Increase blower speed or reduce restriction - replace air filter

 

Restriction in liquid line,

Replace defective components

High head - Low

metering device or filter drier

 

vapor pressures

Flowrator piston size too small

Change to correct size piston

 

Incorrect capillary tubes

Change coil assembly

 

Blocked outdoor coil

Clear away leaves and other debris

High head - High

Refrigerant overcharge

Correct system charge

or normal vapor

Condenser fan not running

Repair or replace

pressures

Air, non-condensibles or

Recover refrigerant, evacuate &

 

moisture in system

recharge, add filter drier

Low head - High

Flowrator piston size too large

Change to correct size piston

vapor pressures

Defective compressor valves

Replace compressor

 

Incorrect capillary tubes

Replace coil assembly

Low vapor - cool

Low evaporator airflow

Increase blower speed or reduce restriction - replace air filter

compressor - iced

Operating below 65 F outdoors

Add low ambient kit

evaporator coil

Moisture in the system

Recover refrigerant, evacuate & recharge, add filter drier

High vapor

Excessive load

Recheck load calculation

pressure

Defective compressor

Replace

Fluctuating head

Air or non-condensibles in system

Recover refrigerant, evacuate & recharge.

and vapor pressures

 

 

Pulsing noise at

Air or non-condensibles in system

Recover refrigerant, evacuate & recharge

metering device

 

 

or liquid line

 

 

 

 

 

11

Page 14
Image 14
Haier HC1891VAR operation manual Symptom Possible Cause Remedy

HC1891VAR specifications

The Haier HC1891VAR is a versatile and efficient refrigerator designed to cater to the modern household's needs. Known for its innovative technology and user-friendly features, the HC1891VAR stands out in the competitive appliance market.

One of the key features of the Haier HC1891VAR is its spacious interior, which offers ample storage options. With a total capacity of around 18 cubic feet, this refrigerator provides enough room for groceries and perishables, making it ideal for families and individuals who require extra space. The adjustable shelves allow users to customize the interior layout to accommodate various food items of different sizes. Furthermore, the door storage compartments offer convenient access to frequently used items, ensuring you're organized and efficient in the kitchen.

Another hallmark of the HC1891VAR is its advanced cooling technology. The refrigerator is equipped with a multi-flow air system, which circulates cool air evenly throughout the compartments. This feature helps maintain optimal temperature levels, ensuring that food stays fresh for longer periods. Additionally, the model employs a frost-free operation that eliminates the need for manual defrosting, saving time and effort while ensuring a hassle-free experience.

The Haier HC1891VAR also focuses on energy efficiency. It is designed to consume less energy compared to traditional refrigerators, earning it an Energy Star rating. This not only contributes to lower electricity bills but also showcases Haier's commitment to environmentally friendly practices. The eco-friendly refrigerant used in the HC1891VAR further enhances its sustainability credentials.

For convenience, the HC1891VAR boasts user-friendly temperature controls that allow for precise adjustments. The LED interior lighting illuminates the inside of the refrigerator, making it easy to find items, even in low light. The sleek design and modern finish ensure that it complements any kitchen decor, while its quiet operation guarantees minimal disruption.

In summary, the Haier HC1891VAR is a well-rounded refrigerator that combines ample storage, advanced cooling technology, energy efficiency, and user convenience. Its thoughtful design and innovative features make it a reliable choice for anyone looking to upgrade their kitchen appliances. With the HC1891VAR, Haier continues to uphold its reputation for quality and customer satisfaction in home appliances.