Selection of pipe
Liquid pipe (Ø) | 6.35mm(1/4”) |
|
|
Gas pipe (Ø) | 12.7mm(1/2”) |
|
|
NOTE:The thickness of the pipe must be 0.8mm at least.
Indoor unit
1Fitting of the Mounting Plate and Positioning of the wall Hole
When the mounting plate is first fixed
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2.Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.
3.Find the wall hole location A using a measuring tape
B= 60mm
A=145mm | 30mm |
|
B= | 60mm |
A=150mm | 30mm |
|
When the mounting plate is fixed side bar and lintel
●Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten the plate to the fixed mounting bar.
●Refer to the previous article, “ When the mounting plate is first fixed “, for the position of wall hole.
2Making a Hole on the Wall and Fitting the Piping Hole Cover
●Make a hole of 60 mm in diameter, slightly descending to outside the wall.
●Install piping hole cover and seal it off with putty after installation
Wall hole
Ø60mm
Indoor side | Outdoor side |
| Thickness of wall |
(Section of wall hole) | G Piping hole pipe |
3Installation of the Indoor Unit
Drawing of pipe
[ Rear piping ]
●Draw pipes and the drain hose, then fasten them with the adhesive tape
[ Left·Left-rear piping ]
●In case of left side piping, cut away, with a nipper, the lid for left piping.
●In case of
the mark of hole for
1.Insert the drain hose into the dent of heat insulation materials of indoor unit.
2.Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then connect them.
3.Coat the flaring seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape
|
|
| Indoor/outdoor electric cable |
|
| Heat insulation | Piping |
|
| material | |
Lid for right |
|
| Pipe supporting |
piping | Lid for left piping | Drain hose | plate |
|
| ||
|
|
| |
Lid for under piping pipe |
|
|
|
Fix with adhesive tape
●Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.
[ Other direction piping ]
●Cut away, with a nipper, the lid for piping according to the piping direction and
then bend the pipe according to theposition of wall hole. When bending, be careful not to crash pipes.
●Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation of connecting part specially.
Fixing the indoor unit body
●Hang surely the unit body onto the upper notches of the mounting plate. Move the body from side to side to verify its secure fixing.
● In order to fix the body onto the mounting plate,hold up |
|
the body aslant from the underside and then put it down |
|
perpendicularly. | mounting plate |
Unloading of indoor unit body
●When you unload the indoor unit,please use your hand to arise the body to leave agraffe,
then lift the bottom of the body outward slightly and lift the unit aslant until it leaves the mounting plate.
agraffe mounting plate
4Connecting the indoor/outdoor Electric Cable Removing the wiring cover
●Remove terminal cover at right bottom corner of indoor unit, then take off wiring cover by removing its screws.
When connecting the cable after installing the indoor unit
1. Insert from outside the room cable into left side of the wall
hole, in which the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable making a loop.
When connecting the cable before installing the indoor unit
●Insert the cable from the back side of the unit, then pull it out on the front side.
●Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.
●Pull the cable slightly to make sure the cables have been properly inserted and tightened.
●After the cable connection, never fail to fasten the connected cable with the wiring cover.
Note | When connecting the cable, confirm the terminal number of indoor and |
| outdoor units carefully. If wiring is not correct, proper operation can not |
| be carried out and will cause defect. |